Hazardous Location - European and International Approval (ATEX, IECEx)
Section 2 Hardware
26
3BDD011677-600 A
Hazardous Location - European and International Approval (ATEX, IECEx)
If indicated on the device label or by technical documentation linking device LD
800HSE EX is suitable for use in gas- Ex atmospheres of Zone 2 in the explosion
groups IIA, IIB and IIC in temperature class T4, if accommodated in a tested
enclosure.
The linking device LD 800HSE EX complies with the applicable standards and
regulations, and meets the requirements of Directive 94/4EC. The requirements for
erecting the device as part of the system in potentially explosive atmospheres (e.g.
IEC / EN 60079-14) must be strictly adhered.
Explosion hazard - Do not disconnect equipment unless power has been removed
or the area is known to be non-hazardous.
Explosion hazard - Substitution of any components may impair suitability for
Class I, Division 2.
Permitted ambient temperature range:
0°C
≤
Ta
≤
55°C
IECEx marking for explosion protection:
Ex nA IIC T4 Gc
ATEX marking for explosion protection:
II 3G nA IIC T4 Gc
‘
For general requirements, rules for installing, commissioning, maintaining and
the appropriate use of LD 800HSE EX in hazardous atmospheres, refer to
Appendix D, Linking Device for Zone 2 Explosion and Protection Environment
Содержание LD 800HSE
Страница 2: ......
Страница 3: ...Device Management FOUNDATION Fieldbus Linking Device LD 800HSE and LD 800HSE EX V3 6 0 0 ...
Страница 78: ...Built in Web Server Section 4 Linking Device Diagnostics 78 3BDD011677 600 A Figure 24 LD 800HSE Contact Page ...
Страница 94: ...Linking Device Web Server Diagnostics Section 4 Linking Device Diagnostics 94 3BDD011677 600 A ...
Страница 102: ...Device Redundancy Appendix B Limits and Performance Data 102 3BDD011677 600 A ...
Страница 124: ...Redundancy Behavior Appendix C Technical Reference 124 3BDD011677 600 A ...
Страница 135: ......