Section 2 Hardware InstallationReplacing a Defective Linking Device in a Redundant Set of Linking
3BDD011677-600 A
45
Replacing a Defective Linking Device in a Redundant Set
of Linking Devices
For replacing a defective linking device in a redundant set of linking devices,
perform the following steps:
1.
Identify the defective linking device, refer to
2.
Remove the power terminal block from the linking device.
3.
Remove the RS-232 cable (redundancy link) and the Ethernet cable.
4.
If not indicated on the cable, make a note to which channel each H1 link is
connected. Then remove the H1 terminal blocks.
5.
Make sure that the new linking device has the same IP configuration (IP
address and subnet mask) as the replaced defective device, see
6.
Replace the defective linking device.
7.
Plug in the H1 terminal blocks. Make sure to use the same allocation as before
8.
Connect the Ethernet cable and the RS-232 cable.
9.
Plug in the power terminal block. The boot process and the download of the
configuration information take about 1 minute. For indication of proper
operation as a Secondary Device, refer to
Make sure not to permute the H1 terminal blocks! An accidental permutation of
the H1 link connections at the secondary linking device will not be detected right
away. On application level detection will not be possible before a redundancy
switch-over takes place or the live lists of primary and secondary linking device
are being compared manually.
Make sure that the RS-232 cable is connected before plugging in the power
terminal block.
If the replaced linking device is powered while the serial link is missing, it will
behave like an independent, non-redundant Primary Device. If in this case the
linking device has a valid (possibly unknown) configuration, it might use H1
node addresses which are already in use on the H1 links. This will disturb or
interrupt communication and application processing on the H1 links.
Содержание LD 800HSE
Страница 2: ......
Страница 3: ...Device Management FOUNDATION Fieldbus Linking Device LD 800HSE and LD 800HSE EX V3 6 0 0 ...
Страница 78: ...Built in Web Server Section 4 Linking Device Diagnostics 78 3BDD011677 600 A Figure 24 LD 800HSE Contact Page ...
Страница 94: ...Linking Device Web Server Diagnostics Section 4 Linking Device Diagnostics 94 3BDD011677 600 A ...
Страница 102: ...Device Redundancy Appendix B Limits and Performance Data 102 3BDD011677 600 A ...
Страница 124: ...Redundancy Behavior Appendix C Technical Reference 124 3BDD011677 600 A ...
Страница 135: ......