Appendix B Limits and Performance Data
Limits of the Linking Device on HSE
3BDD011677-600 A
97
Appendix B Limits and Performance Data
Limits of the Linking Device on HSE
Maximum Limits
Performance of HSE communication
For System 800xA SV5.1 onwards,
Signal Transfer between HSE and H1 is able to
handle a maximum of 160 signals per second between all four H1 links and the HSE
network, while 4*16 client/server connections can be used parallel. For availability
with other system environments, check corresponding system release notes.
Maximum Limits of the Linking Device on HSE
Configured HSE sessions
64
Configured HSE VCRs
400
Automatic HSE sessions
32
Automatic HSE VCRs
256
H1-H1 republishings
64
In ABB system environments, the configuration tools Fieldbus Builder
FOUNDATION Fieldbus and Control Builder F will take these limits into
account automatically, depending on the capability of the system version and if
not noted otherwise.