Login to Web Server Interface
Section 3 Configuration
62
3BDD011677-600 A
•
The Maintenance IP Address is required to download the linking device
firmware from a maintenance server. The maintenance server is a TFTP server
(Tiny File Transfer Protocol) that contains an image of the flash memory
content of the linking device and a batch file. It is also possible to download a
new firmware from your PC by means of a web browser. In that case it is not
necessary to install a maintenance server and to specify its address.
When the entries are complete, click the Submit and Reboot button.
The input values will be checked for consistency. If the input values are not
consistent, the linking device will propose consistent values. You can use the
proposed values by clicking Yes or keep at the values you entered by selecting No,