Display Elements
Section 2 Hardware Installation
42
3BDD011677-600 A
Status Indications of the four H1 Channels
F
red
Inactive device, duplicate H1 address.
The device is inactive on HSE and affected H1 links, because a
device with the H1 address of the linking device has been
detected on at least one H1 link during startup.
If the device is part of a redundant set, this state may be caused
by interruption of the serial communication between the two
linking devices during startup. After the serial communication is
reestablished, the device with the duplicate H1 address error will
reboot and receive configuration data from the Primary Device.
R
Table 9. Status Indication of H1 Channels
Display
Element
Description
1
Status of H1 Channel 1
green
Device acts as Link Active Scheduler (LAS) on channel H1-1 (FF 1).
green
Device is in logical token ring but does not act as LAS on channel
H1-1 (FF 1).
Channel H1-1 (FF 1) is not configured.
2
Status of H1 Channel 2
green
Device acts as Link Active Scheduler (LAS) on channel H1-2 (FF 2).
green
Device is in logical token ring but does not act as LAS on channel
H1-2 (FF 2).
Channel H1-2 (FF 2) is not configured.
3
Status of H1 Channel 3
green
Device acts as Link Active Scheduler (LAS) on channel H1-3 (FF 3).
Table 8. Device Status Indication with Two-colored F- and R-LEDs
Display
Element
Description
Содержание LD 800HSE
Страница 2: ......
Страница 3: ...Device Management FOUNDATION Fieldbus Linking Device LD 800HSE and LD 800HSE EX V3 6 0 0 ...
Страница 78: ...Built in Web Server Section 4 Linking Device Diagnostics 78 3BDD011677 600 A Figure 24 LD 800HSE Contact Page ...
Страница 94: ...Linking Device Web Server Diagnostics Section 4 Linking Device Diagnostics 94 3BDD011677 600 A ...
Страница 102: ...Device Redundancy Appendix B Limits and Performance Data 102 3BDD011677 600 A ...
Страница 124: ...Redundancy Behavior Appendix C Technical Reference 124 3BDD011677 600 A ...
Страница 135: ......