Section 3 Configuration
Login to Web Server Interface
3BDD011677-600 A
69
Different or Unknown Configuration File Formats.
1.
Update the firmware in either of the devices making up the redundant set,
using the web interface, refer to
on page 65, but do not
download configuration data.
2.
Update the firmware in the remaining device using the web interface.
3.
Wait until both devices have completed rebooting.
4.
Download configuration data to the redundant set of devices.
Updating Firmware from 1.50.1.02 to Latest Version.
For updating linking devices with firmware from 1.50.1.02 to latest version, the
normal procedure applies as described in
When updating a redundant set of linking devices, follow the procedure of
subsection
on page 67 as described in the following subsection
Identical Configuration File Formats.
The following procedure works regardless of the file formats of the old and new
firmware release. As HSE and H1 communication will be stopped for the affected
redundant set of linking devices, it is not recommended to apply this
procedure to an operating set of devices.
Applying the following procedure for a firmware update on an operating
redundant set of linking devices stops all HSE republishing and cyclical
communication on all H1 links of that set of linking devices as well as
client/server communication to the linking device and the devices on the H1
links. No cyclical or client/server communication on the H1 links of the affected
redundant set of linking devices is possible until configuration data has been
downloaded to the redundant set of devices.
Downloading configuration data to a linking device requires the following steps
to be carried out in the ABB configuration tools:
•
initialization and address assignment of the linking device and
•
download of the linking device.
It is not required to re-assign or load H1 devices after a firmware update of a
linking device.
Содержание LD 800HSE
Страница 2: ......
Страница 3: ...Device Management FOUNDATION Fieldbus Linking Device LD 800HSE and LD 800HSE EX V3 6 0 0 ...
Страница 78: ...Built in Web Server Section 4 Linking Device Diagnostics 78 3BDD011677 600 A Figure 24 LD 800HSE Contact Page ...
Страница 94: ...Linking Device Web Server Diagnostics Section 4 Linking Device Diagnostics 94 3BDD011677 600 A ...
Страница 102: ...Device Redundancy Appendix B Limits and Performance Data 102 3BDD011677 600 A ...
Страница 124: ...Redundancy Behavior Appendix C Technical Reference 124 3BDD011677 600 A ...
Страница 135: ......