Display Elements
Section 2 Hardware Installation
40
3BDD011677-600 A
Device Status Indication (Two-colored F- and R-LEDs)
Table 8. Device Status Indication with Two-colored F- and R-LEDs
Display
Element
Description
P
P - Power Supply
No supply voltage.
green
Supply voltage is present.
HSE
HSE - Ethernet Port
No Ethernet link established.
green
Ethernet link has been established
(10 Mbit/s or 100 Mbit/s).
green
Device is transmitting Ethernet frames.
F / R
F - Error Status / R - Ready for Operation
F
Initial boot phase (approx. 7 seconds).
During this phase the boot process may be stopped via the serial
interface.
R
green
F
Start-up phase (approx. 25 seconds).
During this phase the power-on self tests are executed and the
redundancy role is determined.
R
F
red
Permanent hardware fault detected during startup.
A fatal error has been detected during power-on self tests, refer
to
R
F
Non-redundant device, ready.
The device is operational; it is not part of a redundant set.
R
green
F
green
Primary Device in redundant set.
The device is operational, acting as Primary Device in a
redundant set. The Secondary Device is ready.
R
green
Содержание LD 800HSE
Страница 2: ......
Страница 3: ...Device Management FOUNDATION Fieldbus Linking Device LD 800HSE and LD 800HSE EX V3 6 0 0 ...
Страница 78: ...Built in Web Server Section 4 Linking Device Diagnostics 78 3BDD011677 600 A Figure 24 LD 800HSE Contact Page ...
Страница 94: ...Linking Device Web Server Diagnostics Section 4 Linking Device Diagnostics 94 3BDD011677 600 A ...
Страница 102: ...Device Redundancy Appendix B Limits and Performance Data 102 3BDD011677 600 A ...
Страница 124: ...Redundancy Behavior Appendix C Technical Reference 124 3BDD011677 600 A ...
Страница 135: ......