Maintenance and Repair
Appendix D Linking Device for Zone 2 Explosion and Protection
130
3BDD011677-600 A
•
The equipment must be serviced and cleaned regularly inside the Ex-
atmosphere. The intervals must be defined by the operator in compliance with
the environmental rules valid at the place of operation.
•
After maintenance and repair works have been performed, all barriers and sign
boards used for that purpose must be restored in their original place.
•
In case faults of the equipment are noticed, remove the equipment. The inner
parts cannot be maintained by the customer. Instead, send the equipment to the
manufacturer for inspection.
The following table details the frequency of inspection for LD 800HSE EX device:
Activity
Monthly Visual
Inspection
Close Inspection
every 6 Months
Detailed Inspection
every 12 Months
Visual inspection of lining
device for intactness, removal
of dust settlement.
•
Yes
(1)
(1) Frequency can be shortened or extended considering the local conditions.
Check of entire system
Operator’s responsibility