H1 Diagnostics
Section 4 Linking Device Diagnostics
84
3BDD011677-600 A
H1 Diagnostics
shows an example of the H1 Diagnostics web page which provides access
to error counters for framing errors and checksum errors on the H1 channels as
explained in
.
Increasing values of these counters point at physical network problems like
•
EMC interference
•
Loose connection
•
Shielding problems
•
Termination problems
•
Crosstalk from adjacent cables.
Besides useful diagnostics during commissioning, this information can also be used
to detect deteriorating wiring conditions in the plant before the process is affected.
For resetting the error counters click the Reset Error Counters button.
Figure 27. H1Diagnostics