Commissioning
JRA/S 6.230.3.1 | 2CDC506083D0201 79
"Switch 3"
Notes
The parameter descriptions for
"Switch 3"
are the same as for
"Switch 2"
.
"Block" 1 Bit
Options:
No
Yes
•
Yes:
The 1-bit group object
Block
is enabled. This can be used to disable the input.
Notes
If the input is disabled and the option
Send cyclically
is set, the last state is still sent regardless of the
block. The
Block
option still blocks the physical input, sending continues internally.
"Start event 0/1" 1 bit
Options:
No
Yes
•
Yes:
The 1-bit group object
Start event 0/1
is enabled. As a result, the same events, such as those of
the button/switch connected to the binary input, can also be triggered by receipt of a telegram on the
Start event 0/1
group object.