![ABB i-bus KNX JRA/S 6.230.3.1 Скачать руководство пользователя страница 114](http://html.mh-extra.com/html/abb/i-bus-knx-jra-s-6-230-3-1/i-bus-knx-jra-s-6-230-3-1_product-manual_3075114.webp)
ABB i-bus
®
KNX
Commissioning
112 2CDC506083D0201 | JRA/S 6.230.3.1
No.
Function
Object name
Data type
Flags
82
Sun
Blind Output A,B
Shutter Output A,B
1 bit
DPT 1.001
C, W
This group object is enabled if the
Enable function Automatic
parameter is set to
Yes
in the
A, B: Blind
parameter window.
This group object activates sun protection: The blind moves to the sun screening position.
Incoming telegrams on this group object are only considered if the group object
Activation of autom. control
has the value 1.
If the
Sun
group object receives a telegram with the value 1, the blind moves to the parametrized position for Sun = 1. If the
object receives a telegram with the value 0, the blind moves to the parametrized position for sun = 0.
The execution of a reaction to incoming telegrams can be delayed via the parameter Delay for sun = 1 and Delay for sun = 0,
in order to prevent the shutters/blinds continuously moving up and down in changeable weather. If a telegram with the
opposing value is received within the delay time, Position for sun = 1 is not executed and the blind remains in the Position for
sun = 0 position or vice versa.
If Position for sun = 1 is set to
Receive position via 8-bit values
, then once the delay has elapsed, the output moves to the last
position received on the group objects
Move to pos. for sun [0..255]
(blinds and shutters) and
Adjust slat for sun [0…255]
(blinds only).
Telegram value:
0 = no sun
1 = sun
83
Move to pos. for sun
Blind Output A,B
Shutter Output A,B
1 byte
DPT 5.001
C, W
This group object is enabled if the
Enable function Automatic
parameter is set to
Yes
in the
A, B: Blind
parameter window.
This group object sets the position during active sun protection.
Incoming telegrams on this group object are only executed immediately if automatic control is activated (Activation of autom.
control = 1) and the sun is shining (sun = 1). The blind is then positioned according to the received value.
Telegram value:
0
= upper
…
= Intermediate position
255 = lower
84
Sun slat adjust.
Blind Output A,B
1 byte
DPT 5.001
C, W
This group object is enabled if the
Enable function Automatic
parameter is set to
Yes
in the
A, B: Blind
parameter window.
This group object sets the slat position during active sun protection and is thus only available with blind operation.
Incoming telegrams on this group object are only executed immediately if automatic control is activated (Activation of autom.
control = 1) and the sun is shining (sun = 1). The slats are then positioned according to the received value.
The Move telegram
Move to pos. for sun [0..255]
is always moved to the target position before the positioning of the slats is
executed.
Telegram value:
0
= slats fully OPEN
…
= Intermediate position
255 = slats CLOSED
Содержание i-bus KNX JRA/S 6.230.3.1
Страница 1: ...ABB i bus KNX JRA S 6 230 3 1 Blind Roller Shutter Actuator with Binary Inputs Product Manual ...
Страница 2: ......
Страница 8: ...ABB i bus KNX General 6 2CDC506083D0201 JRA S 6 230 3 1 ...
Страница 14: ...ABB i bus KNX Device technology 12 2CDC506083D0201 JRA S 6 230 3 1 2 3 Dimension drawing 2CDC072028F0016 ...
Страница 142: ......
Страница 148: ...ABB i bus KNX Appendix 146 2CDC506083D0201 JRA S 6 230 3 1 Notes ...
Страница 149: ...ABB i bus KNX Appendix JRA S 6 230 3 1 2CDC506083D0201 147 Notes ...
Страница 150: ...ABB i bus KNX Appendix 148 2CDC506083D0201 JRA S 6 230 3 1 Notes ...
Страница 151: ......