Commissioning
106 2CDC506083D0201 | JRA/S 6.230.3.1
3.4.4.2
Output A group objects
No.
Function
Object name
Data type
Flags
75
Switch
Output A
1 bit
DPT 1.001
C, W
This group object is enabled if the
Mode Output
parameter is set to
Switch actuator
in the
Output A, B: Mode
parameter
window.
This group object switches the output ON/OFF. The device receives a Switch telegram via the Switch group object.
N/O:
Telegram value
1 = switch ON
0 = Switch OFF
N/C:
Telegram value
1 = switch OFF
0 = Switch ON
Note
With logical connections or forced operations, a change in the
Switch
group object does not necessarily result in a
changed contact position.
For further information see: Function diagram, p. 126
76
Permanent on
Output A
1 bit
DPT 1.003
C, W
This group object is enabled if the
Enable function Time
parameter is set to
Yes
in the
Output A,B: Switch actuator
parameter
window.
If the communication object is assigned with the value 1, the output is switched on irrespective of the value of the
communication object
Switch
and remains switched on until the communication object
Permanent ON
has the value 0. When
the Permanent ON state ends, the state of the communication object
Switch
is used.
Permanent ON only switches ON and "masks" the other functions. This means that the other functions, e.g. Staircase lighting,
continue to run in the background but do not initiate a switching action. When permanent ON ends, the contact position which
would result without the permanent ON function becomes active. For the
Staircase lighting
function the reaction after
Permanent ON is parametrized in
This communication object can be used, for example, to allow service or maintenance and cleaning personnel to initiate a
permanent ON. The device receives a switch telegram via the switch object.
Permanent ON becomes inactive after a download or bus voltage recovery.
Telegram value
1 = activates permanent ON mode
0 = Deactivates permanent ON mode
Содержание i-bus KNX JRA/S 6.230.3.1
Страница 1: ...ABB i bus KNX JRA S 6 230 3 1 Blind Roller Shutter Actuator with Binary Inputs Product Manual ...
Страница 2: ......
Страница 8: ...ABB i bus KNX General 6 2CDC506083D0201 JRA S 6 230 3 1 ...
Страница 14: ...ABB i bus KNX Device technology 12 2CDC506083D0201 JRA S 6 230 3 1 2 3 Dimension drawing 2CDC072028F0016 ...
Страница 142: ......
Страница 148: ...ABB i bus KNX Appendix 146 2CDC506083D0201 JRA S 6 230 3 1 Notes ...
Страница 149: ...ABB i bus KNX Appendix JRA S 6 230 3 1 2CDC506083D0201 147 Notes ...
Страница 150: ...ABB i bus KNX Appendix 148 2CDC506083D0201 JRA S 6 230 3 1 Notes ...
Страница 151: ......