![ABB i-bus KNX JRA/S 6.230.3.1 Скачать руководство пользователя страница 43](http://html.mh-extra.com/html/abb/i-bus-knx-jra-s-6-230-3-1/i-bus-knx-jra-s-6-230-3-1_product-manual_3075043.webp)
ABB i-bus
®
KNX
Commissioning
JRA/S 6.230.3.1 | 2CDC506083D0201 41
Enable communication object
"Status Switch" 1-bit
Options:
No
Yes
Caution
If an internal connection with an output is selected, and at the same time the reaction to an event is
parametrized with TOGGLE, the binary input's
Switch 1
group object is updated with the inverted value
of the output's
Status Switch
group object.
Ensure that the output's
Status Switch
group object is enabled. The
N/C / N/O
settings should be
parametrized so that TOGGLE is possible.
•
Yes
: The following parameters appear:
Send object value
Options:
No, update only
On change
After request
After a change or request
•
No, update only
: The status is updated but not sent.
•
On change
: The status is sent when a change occurs.
•
After request
: The status is sent when a request occurs.
•
After a change or request
: The status is sent on a change or a request.
Object value of contact position
Options:
1=closed, 0=open
0 = closed, 1 = open
This parameter defines the communication object value of the switch status (
Status switch
).
•
1 = Closed, 0 = Open:
A closed contact is represented by group object value 1 and an open
contact is represented by the value 0.
•
0 = Closed, 1 = Open:
A closed contact is represented by group object value 0 and an open
contact is represented by the value 1.
Note
The contact position and thus the switch status can be the result of a series of priorities and
connections.
Содержание i-bus KNX JRA/S 6.230.3.1
Страница 1: ...ABB i bus KNX JRA S 6 230 3 1 Blind Roller Shutter Actuator with Binary Inputs Product Manual ...
Страница 2: ......
Страница 8: ...ABB i bus KNX General 6 2CDC506083D0201 JRA S 6 230 3 1 ...
Страница 14: ...ABB i bus KNX Device technology 12 2CDC506083D0201 JRA S 6 230 3 1 2 3 Dimension drawing 2CDC072028F0016 ...
Страница 142: ......
Страница 148: ...ABB i bus KNX Appendix 146 2CDC506083D0201 JRA S 6 230 3 1 Notes ...
Страница 149: ...ABB i bus KNX Appendix JRA S 6 230 3 1 2CDC506083D0201 147 Notes ...
Страница 150: ...ABB i bus KNX Appendix 148 2CDC506083D0201 JRA S 6 230 3 1 Notes ...
Страница 151: ......