ABB i-bus
®
KNX
Commissioning
52 2CDC506083D0201 | JRA/S 6.230.3.1
Assignment to scene number
(No. 1...64, 0 = no assignment)
Options:
0…64
The
Scene
function manages up to 64 scenes using one single group address. With this group address, all
slaves integrated into a scene are linked via a 1-byte group object. The following information is contained
in a telegram:
•
Scene number (1…64) and
•
Telegram: Recall scene or Store scene.
The output can be integrated in up to eight scenes. So for example, the output can be switched on by a
scene in the morning and switched off in the evening, or it can be integrated into light scenes.
If a telegram is received on the
Scene
group object, on all outputs assigned to the sent scene number the
blind moves to the stored scene position or stores the current position as the new scene position.
Standard value
Options:
ON
OFF
Here you set the state that the output has when the scene is recalled.
Note
When a scene is recalled:
•
the
Time
function is restarted
•
the logical connections are re-evaluated
For further information see: Group objects Output A, p. 106, Scene function, p. 133 and Code table, 8 bit scene, p. 143.
Содержание i-bus KNX JRA/S 6.230.3.1
Страница 1: ...ABB i bus KNX JRA S 6 230 3 1 Blind Roller Shutter Actuator with Binary Inputs Product Manual ...
Страница 2: ......
Страница 8: ...ABB i bus KNX General 6 2CDC506083D0201 JRA S 6 230 3 1 ...
Страница 14: ...ABB i bus KNX Device technology 12 2CDC506083D0201 JRA S 6 230 3 1 2 3 Dimension drawing 2CDC072028F0016 ...
Страница 142: ......
Страница 148: ...ABB i bus KNX Appendix 146 2CDC506083D0201 JRA S 6 230 3 1 Notes ...
Страница 149: ...ABB i bus KNX Appendix JRA S 6 230 3 1 2CDC506083D0201 147 Notes ...
Страница 150: ...ABB i bus KNX Appendix 148 2CDC506083D0201 JRA S 6 230 3 1 Notes ...
Страница 151: ......