ABB i-bus
®
KNX
Commissioning
100 2CDC506083D0201 | JRA/S 6.230.3.1
3.4.3.1
group objects Switch sensor
No.
Function
Object name
Data type
Flags
10
Block
Input a: Switch sensor
1 bit
DPT 1.003
C, W
This group object is enabled if the
Enable group object "Block" 1 bit
parameter is set to
Yes
in the
Input
a: Switch sensor
parameter window.
Using the communication object
Block
, the input can be blocked or enabled. With activated communication object
Block
the
inputs are blocked.
Note
When the input is blocked there is fundamentally no reaction to a signal change on the input, but:
– Waiting for a long button operation or a minimum signal duration is suspended.
– Parametrized
Cyclic sending
is not interrupted.
– It is still possible to write the
Switch x
group object.
If the input state changed during the blocked phase, this leads to immediate sending of the new communication
object value after enabling. If the input state remains the same during the blocking phase, the communication object
value is not sent.
Telegram value:
0 = enable input a
1 = Block input a
11
Switch 1
Input a: Switch sensor
1 bit
DPT 1.001
C, W, T
This group object is enabled if the
Function
parameter is set to
Switch sensor
in the
Input a
:
Function
parameter window and
the “
Switch 1
” parameter is set to
Yes
in the
Input a
:
Objects “Switch”
parameter window.
In accordance with the parameter setting, this group object can be switched by actuating the input to
ON, OFF
or
TOGGLE
or
can be set to
No reaction
. With toggle the previous value, e.g. 1, is toggled directly to the value 0. The group object can be
sent cyclically, e.g. for sensor lifesign monitoring.
Note
The communication object can be written to externally. Thus cyclic sending is interrupted or may not be possible
depending on the parameter setting.
No further group objects are visible with the setting.
Telegram value:
0 = OFF
1 = ON
12
13
Switch 2
Switch 3
See communication object 46.
14
Start event 0/1
Input a: Switch sensor
1 bit
DPT 1.001
C, W
This group object is enabled if the
"Start event 0/1" 1 bit
parameter is set to
Yes
in the
Input a: Switch sensor
parameter
window.
The 1-bit communication object
Start event 0/1
is enabled. As a result, the same events, except those of the push
button/switch connected to the binary input, can also be triggered by the receipt of a telegram on the communication object
Start event 0/1
.
Telegram value:
0 = start event 0
1 = Start event 1
Содержание i-bus KNX JRA/S 6.230.3.1
Страница 1: ...ABB i bus KNX JRA S 6 230 3 1 Blind Roller Shutter Actuator with Binary Inputs Product Manual ...
Страница 2: ......
Страница 8: ...ABB i bus KNX General 6 2CDC506083D0201 JRA S 6 230 3 1 ...
Страница 14: ...ABB i bus KNX Device technology 12 2CDC506083D0201 JRA S 6 230 3 1 2 3 Dimension drawing 2CDC072028F0016 ...
Страница 142: ......
Страница 148: ...ABB i bus KNX Appendix 146 2CDC506083D0201 JRA S 6 230 3 1 Notes ...
Страница 149: ...ABB i bus KNX Appendix JRA S 6 230 3 1 2CDC506083D0201 147 Notes ...
Страница 150: ...ABB i bus KNX Appendix 148 2CDC506083D0201 JRA S 6 230 3 1 Notes ...
Страница 151: ......