![ABB i-bus KNX JRA/S 6.230.3.1 Скачать руководство пользователя страница 104](http://html.mh-extra.com/html/abb/i-bus-knx-jra-s-6-230-3-1/i-bus-knx-jra-s-6-230-3-1_product-manual_3075104.webp)
ABB i-bus
®
KNX
Commissioning
102 2CDC506083D0201 | JRA/S 6.230.3.1
3.4.3.3
Blind sensor group objects
No.
Function
Object name
Data type
Flags
10
Block
Input a:
Blind sensor
1 bit
DPT 1.003
C, W
This group object is enabled if the
Enable group object "Block" 1 bit
parameter is set to
Yes
in the
Input a: Blind sensor
parameter window.
Using the communication object
Block
, the input can be blocked or enabled. With activated communication object
Block
the
inputs are blocked.
Note
When the input is blocked there is fundamentally no reaction to a signal change, but:
– Waiting for a long button operation or a minimum signal duration is suspended.
– Parametrized
Cyclic sending
is interrupted.
– Group objects continue to be updated and sent if necessary.
When enabling an input, a change of the signal states (as opposed to before the block) leads to immediate
processing, e.g.:
– The minimum actuation or detection of a long/short button push starts.
– Group objects send their current value if necessary.
Telegram value:
0 = enable input a
1 = Block input a
11
Blind UP/DOWN
Input a:
Blind sensor
1 bit
DPT 1.008
C, W, T
This group object is enabled if the
Function
parameter is set to
Blind sensor
in the
Input a
:
Function
parameter window.
This group object sends a blind UP or DOWN Move telegram on the bus. By receiving telegrams, the device also recognizes
Move telegrams from another sensor, e.g. parallel operation.
Telegram value
0 = UP
1 = DOWN
12
STOP/slat adjustment
Input a:
Blind sensor
1 bit
DPT 1.007
C, T
This group object is enabled if the
Function
parameter is set to
Blind sensor
in the
Input a
:
Function
parameter window.
This communication object sends a STOP telegram or slat adjustment.
Telegram value
0 = STOP/slat adjustment UP
1 = STOP/slat adjustment DOWN
Содержание i-bus KNX JRA/S 6.230.3.1
Страница 1: ...ABB i bus KNX JRA S 6 230 3 1 Blind Roller Shutter Actuator with Binary Inputs Product Manual ...
Страница 2: ......
Страница 8: ...ABB i bus KNX General 6 2CDC506083D0201 JRA S 6 230 3 1 ...
Страница 14: ...ABB i bus KNX Device technology 12 2CDC506083D0201 JRA S 6 230 3 1 2 3 Dimension drawing 2CDC072028F0016 ...
Страница 142: ......
Страница 148: ...ABB i bus KNX Appendix 146 2CDC506083D0201 JRA S 6 230 3 1 Notes ...
Страница 149: ...ABB i bus KNX Appendix JRA S 6 230 3 1 2CDC506083D0201 147 Notes ...
Страница 150: ...ABB i bus KNX Appendix 148 2CDC506083D0201 JRA S 6 230 3 1 Notes ...
Страница 151: ......