Commissioning
46 2CDC506083D0201 | JRA/S 6.230.3.1
Switching delays retriggerable
Options:
No
Yes
•
No
: The delay time cannot be retriggered.
•
Yes
: The delay time can be retriggered.
Object value "Disable function Time"
on bus voltage recovery
Options:
Unchanged
1, i.e., disable function Time
0, i.e., enable function Time
This parameter defines how the
Time
function should react after bus voltage recovery. The
Time
function
can be disabled or enabled with a telegram to the
Disable function Time
group object.
•
Unchanged
: After bus voltage recovery, the
Time
function reacts in the same way as before bus
voltage failure.
•
1, i.e., disable function time
: A telegram with the value 1 disables the
Time
function.
•
0, i.e., enable function time
: A telegram with the value 0 enables the
Time
function.
Содержание i-bus KNX JRA/S 6.230.3.1
Страница 1: ...ABB i bus KNX JRA S 6 230 3 1 Blind Roller Shutter Actuator with Binary Inputs Product Manual ...
Страница 2: ......
Страница 8: ...ABB i bus KNX General 6 2CDC506083D0201 JRA S 6 230 3 1 ...
Страница 14: ...ABB i bus KNX Device technology 12 2CDC506083D0201 JRA S 6 230 3 1 2 3 Dimension drawing 2CDC072028F0016 ...
Страница 142: ......
Страница 148: ...ABB i bus KNX Appendix 146 2CDC506083D0201 JRA S 6 230 3 1 Notes ...
Страница 149: ...ABB i bus KNX Appendix JRA S 6 230 3 1 2CDC506083D0201 147 Notes ...
Страница 150: ...ABB i bus KNX Appendix 148 2CDC506083D0201 JRA S 6 230 3 1 Notes ...
Страница 151: ......