90 Communication profiles
7
RESET
0=>1 Fault reset if an active fault exists. Proceed
to
SWITCH-ON INHIBITED
.
Note:
This bit is effective only if the
fieldbus interface is set as the source for
this signal by drive parameters.
0
Continue normal operation.
8…9 Reserved.
10
REMOTE_
CMD
1
Fieldbus control enabled.
0
Control
w
ord and reference not getting
through to the drive, except for CW bits
OFF1, OFF2 and OFF3.
11
EXT_CTRL_
LOC
1
Select External Control Location EXT2.
Effective if the control location
parameterized to be selected from the
fieldbus.
0
Select External Control Location EXT1.
Effective if the control location
parameterized to be selected from the
fieldbus.
12…
15
Reserved.
Bit
Name
Value
STATE/Description