Start-up 67
The start sequence for the parameter example above is given
below.
Control word:
•
47Eh (1150 decimal) –> READY TO SWITCH ON
•
47Fh (1151 decimal) –> OPERATING (Speed mode)
or
C7Fh (3199 decimal) –> OPERATING (Torque mode)
ODVA AC/DC drive profile
The following example shows how to configure the ACS880 drive
to use the ODVA AC/DC drive profile.
The used I/O assembly instances are 23 and 73.
19.11 Ext1/Ext2 selection
2
= MCW bit11: Ext
ctrl
Selects FBA Control word bit 11 as
the source for the external control
location EXT1/EXT2 selection.
19.12 Ext1 control mode 1
2
= MCW bit11: Ext
ctrl loc
Selects speed control as the control
mode 1 for external control location
EXT1.
19.14 Ext2 control mode 1
3
= Torque
Selects torque control as the control
mode 1 for external control location
EXT2.
20.01 Ext1 commands
12
= Fieldbus A
Selects fieldbus interface A as the
source of the start and stop
commands for external control
location EXT1.
20.06 Ext2 commands
12
= Fieldbus A
Selects fieldbus interface A as the
source of the start and stop
commands for external control
location EXT2.
22.11 Speed ref1
selection
4
= FB A ref1
Selects fieldbus A reference 1 as the
source for speed reference 1.
26.11 Torque ref1
selection
5
= FB A ref2
Selects fieldbus reference 2 as the
source for torque reference 1.
1)
Read-only or automatically detected/set
2)
Example
Drive parameter
Setting for
ACS880 drives
Description
Содержание FDNA-01
Страница 1: ...Options for ABB drives converters and inverters User s manual FDNA 01 DeviceNet adapter module ...
Страница 2: ...List of related manuals See section Related manuals on page 16 ...
Страница 4: ......
Страница 14: ...14 Safety ...
Страница 22: ...22 About the manual ...
Страница 32: ...32 Electrical installation ...
Страница 72: ...72 Start up 3 Configure the device MAC address ...
Страница 76: ...76 Start up ...
Страница 96: ...96 Communication profiles ...
Страница 154: ...154 Communication protocol ...
Страница 162: ...162 Technical data ...
Страница 166: ...166 Appendix A Varying the number of drive parameters ...