Start-up 45
31
D2FBA COMM
STA
Read-only.
Displays the status of the fieldbus
adapter module communication.
Note:
The value names may vary by drive.
0
= Idle
ACS355:
FBA STATUS
ACSM1:
D2FBA COMM
STA
ACS850/ACQ810/
ACS880:
D2FBA comm sta
0
= Idle
Adapter is not configured.
1
= Exec.init
Adapter is initializing.
2
= Time out
Time-out has occurred in the communication
between the adapter and the drive.
3
= Conf.err
Adapter configuration error: Major or minor
revision code of the common program revision
in the fieldbus adapter module is not the
revision required by the module or mapping file
upload has failed more than three times.
4
= Off-line
Adapter is off-line.
5
= On-line
Adapter is on-line.
6
= Reset
Adapter is performing a hardware reset.
32
FBA COMM SW
VER
Read-only.
Displays the common program
revision of the adapter module in format
axyz
,
where:
a
= major revision number
xy
= minor revision numbers
z
= correction number or letter.
Example: 190A = revision 1.90A
N/A
ACS355:
FBA CPI FW REV
ACSM1:
FBA COMM SW
VER
ACS850/ACQ810/
ACS880:
FBA comm SW
ver
0x0000…0xFFFF
Common program version of the adapter
module
No.
Name/Value
Description
Default
Содержание FDNA-01
Страница 1: ...Options for ABB drives converters and inverters User s manual FDNA 01 DeviceNet adapter module ...
Страница 2: ...List of related manuals See section Related manuals on page 16 ...
Страница 4: ......
Страница 14: ...14 Safety ...
Страница 22: ...22 About the manual ...
Страница 32: ...32 Electrical installation ...
Страница 72: ...72 Start up 3 Configure the device MAC address ...
Страница 76: ...76 Start up ...
Страница 96: ...96 Communication profiles ...
Страница 154: ...154 Communication protocol ...
Страница 162: ...162 Technical data ...
Страница 166: ...166 Appendix A Varying the number of drive parameters ...