Communication profiles 89
2
OFF3_
CONTROL
1
Continue operation (OFF3 inactive).
0
Emergency stop, stop within time defined
with the drive parameter. Proceed to
OFF3
ACTIVE
; proceed to
SWITCH-ON
INHIBITED
.
Warning:
Ensure motor and driven
machine can be stopped using this stop
mode.
3
INHIBIT_
OPERATION
1
Proceed to
OPERATION ENABLED
.
Note:
Run enable signal must be active;
see drive documentation. If the drive is set
to receive the Run enable signal from the
fieldbus, this bit activates the signal.
0
Inhibit operation. Proceed to
OPERATION
INHIBITED
.
4
RAMP_OUT_
ZERO
1
Normal operation. Proceed to
RFG:
OUTPUT ENABLED
.
0
Force the Ramp Function Generator output
to zero. Drive ramps to stop (current and
DC voltage limits in force).
5
RAMP_HOLD
1
Enable ramp function.
Proceed to
RFG: ACCELERATOR
ENABLED
.
0
Halt ramping (Ramp Function Generator
output held).
6
RAMP_IN_
ZERO
1
Normal operation. Proceed to
OPERATION
.
Note:
This bit is effective only if the
fieldbus interface is set as the source for
this signal by drive parameters.
0
Force the Ramp Function Generator input
to zero.
Bit
Name
Value
STATE/Description
Содержание FDNA-01
Страница 1: ...Options for ABB drives converters and inverters User s manual FDNA 01 DeviceNet adapter module ...
Страница 2: ...List of related manuals See section Related manuals on page 16 ...
Страница 4: ......
Страница 14: ...14 Safety ...
Страница 22: ...22 About the manual ...
Страница 32: ...32 Electrical installation ...
Страница 72: ...72 Start up 3 Configure the device MAC address ...
Страница 76: ...76 Start up ...
Страница 96: ...96 Communication profiles ...
Страница 154: ...154 Communication protocol ...
Страница 162: ...162 Technical data ...
Страница 166: ...166 Appendix A Varying the number of drive parameters ...