64 Start-up
Note:
For ACS850 in this example, digital input DI1 has been
configured to control whether to use the speed or torque control
mode.
The start sequence for the parameter example above is given
below.
Control word:
0h (0 decimal) –> READY
1h (1 decimal) –> ENABLED (Running forward)
2h (2 decimal) –> ENABLED (Running reverse)
12.01 Ext1/Ext2 sel
DI1
Selects digital input DI1 as the
source for external control location
EXT1/EXT2 selection (only with
ACS850).
12.05 Ext2 ctrl mode
2
= Torque
Selects torque as the operating
mode for external control location
EXT2 (only with ACS850).
16.15 Menu set sel
(ACS850)
16.21 Menu selection
(ACQ810)
2
= Load long
(ACS850)
1
= Full (ACQ810)
Load long parameter list. All
parameters will be displayed.
21.01 Speed ref1 sel
FBA ref1
Selects the fieldbus reference 1 as
the source for speed reference 1.
24.01 Torq ref1 sel
FBA ref2
Selects fieldbus reference 2 as the
source of the torque reference 1
(only with ACS850).
1)
Read-only or automatically detected/set
Drive parameter
Setting for
ACS850/ACQ810
drives
Description
Содержание FDNA-01
Страница 1: ...Options for ABB drives converters and inverters User s manual FDNA 01 DeviceNet adapter module ...
Страница 2: ...List of related manuals See section Related manuals on page 16 ...
Страница 4: ......
Страница 14: ...14 Safety ...
Страница 22: ...22 About the manual ...
Страница 32: ...32 Electrical installation ...
Страница 72: ...72 Start up 3 Configure the device MAC address ...
Страница 76: ...76 Start up ...
Страница 96: ...96 Communication profiles ...
Страница 154: ...154 Communication protocol ...
Страница 162: ...162 Technical data ...
Страница 166: ...166 Appendix A Varying the number of drive parameters ...