Communication profiles 87
Vector Mode
When the drive is operating in the vector mode, the drive provides
the adapter module with a speed actual. The ODVA AC/DC drive
profile uses rpm units for the speed actual. The ODVA Speed
Actual is calculated as follows:
where
For example, for a drive speed actual of 900 rpm with a unit of 0.5
rpm, the ODVA Speed Actual is:
Torque Actual (AC/DC drive object)
This attribute indicates the actual torque at which the drive is
operating. The units are scaled by the Torque Scale attribute of the
AC/DC drive object. See Table 5. for details.
The drive provides the adapter module with a torque actual in
percent of the motor nominal torque. The ODVA AC/DC drive
profile uses Newton-meter (N·m) units for the Torque Actual. The
ODVA Torque Actual is calculated as follows:
where
Dsa = Drive speed actual in rpm
Osa = ODVA Speed Actual
Us
= ODVA speed unit (see
10
ODVA SPEED SCALE
on page
41
)
Dta = Drive torque actual in percent of motor nominal torque
Ota = ODVA Torque Actual
Ut
= ODVA torque unit
(see
11
ODVA TORQUE SCALE
on page
42
)
Mt
= Motor nominal torque in Nm
Us
Dsa
Osa
=
900
rpm
0.5
rpm
450
Us
Dsa
Osa
=
=
=
Ut
100
Mt
Dta
Ota
×
×
=
Содержание FDNA-01
Страница 1: ...Options for ABB drives converters and inverters User s manual FDNA 01 DeviceNet adapter module ...
Страница 2: ...List of related manuals See section Related manuals on page 16 ...
Страница 4: ......
Страница 14: ...14 Safety ...
Страница 22: ...22 About the manual ...
Страница 32: ...32 Electrical installation ...
Страница 72: ...72 Start up 3 Configure the device MAC address ...
Страница 76: ...76 Start up ...
Страница 96: ...96 Communication profiles ...
Страница 154: ...154 Communication protocol ...
Страница 162: ...162 Technical data ...
Страница 166: ...166 Appendix A Varying the number of drive parameters ...