H3C S12500X-AF & S12500F-AF Interface Module Adapter User Manual-6PW102

H3C S12500X-AF & S12500F-AF 

业务板适配器 用户手册

-6PW102

BOM: 3101A0HE    

The S12500-X LPUs (also called interface modules) are compatible with the S12500X-AF 
switch, but the LPU slots of the S12500X-AF switch are higher and wider than the S12500-X
L P U s . To install an S12500-X LPU on an S12500X-AF switch, install an interface module 
adapter in the LPU slot. 
The S12500-F LPUs (also called interface modules) are compatible with the S12500F-AF 
switch, but the LPU slots of the S12500F-AF switch are higher and wider than the S12500-F
L P U s . To install an S12500- F  LPU on an S12500 F -AF switch, install an interface module 
adapter in the LPU slot.
The interface module adapter provides air vents at the front and rear. Ambient air flows in 
through the air vents at the front.
S12500X-AF

系列交换机兼容

S12500-X

系列交换机适配的业务板(简称

S12500-X

业务板)。

但是,

S12500X-AF

系列交换机业务板槽位比

S12500-X

业务板更高、更宽。因此,当您需要在

S12500X-AF

系列交换机上安装

S12500-X

业务板时,需要先安装业务板适配器。

S12500F-AF

系列交换机上安装

S12500-F

业务板时情况相同,需要先在

S12500F-AF

交换机

业务板槽位上安装业务板适配器。
此外,业务板适配器前面板上侧开有通风孔,冷风可从业务板适配器前面板上的通风孔进入为
设备散热。

Overview 

简介

An interface module adapter is required only when you install an S12500-X LPU on an
S12500X-AF switch or install an S12500-F LPU on an S12500F-AF switch .

仅当在

S12500X-AF

交换机上安装

S12500-X

业务板或在

S12500F-AF

交换机上安装

S12500-F

业务板时才需要安装业务板适配器。

For heat dissipation of the switch, you must install an LPU in the slot where an interface 
module adapter is installed. If you are not to install an LPU in the slot, remove the interface
module adapter and install a filler panel.

安装了业务板适配器的槽位必须安装业务板,如果不需要安装业务板,请拆卸业务板适
配器并安装假面板,否则会影响设备散热。

Interface module adapter view

业务板适配器外观

Screw hole for securing the adapter

to the switch

固定业务板适配器到设备的螺钉孔

Air vents 

前面板通风孔

Screw hole for securing the LPU

固定业务板的螺钉孔

Air vents

后侧顶部通风孔

Wear an ESD wrist strap during the installation and removal procedure and make sure 
the strap has a good skin contact and is reliably grounded.

请在安装过程中佩戴防静电

腕带,确保防静电腕带与皮肤良好接触,并确认防静电腕带已经良好接地。

Tools required 

准备工具

Phillips screwdriver

十字螺丝刀

ESD wrist strap

防静电腕带

If the target slot has a filler panel, remove the filler panel before you install the interface 
module adapter.
Keep the removed filler panel secure for future use.

若待安装业务板的槽位装有假面板,请先将假面板取下,再安装业务板适配器。不准
备安装业务板的槽位请勿拆卸假面板,以免影响设备通风散热。
请妥善保存拆卸下来的假面板,以便将来需要时使用。

Installing an interface module adapter 

安装业务板适配器

!

!

!