Def / Type
FbEq 16b / 32b
Description
Name / Range /
Selection
No.
5
Pt100 sensor connected to a standard analog input
selected by parameter
and an analog output. The input and output can be on
the drive control unit or on an extension module.
The required settings are the same as with selection
, except that the source selection
parameter of the analog output must be set to
.
1 x Pt100 analog I/O
6
As selection
, but with two sensors
connected in series. Using multiple sensors improves
measurement accuracy significantly.
2 x Pt100 analog I/O
7
As selection
, but with three
sensors connected in series. Using multiple sensors
improves measurement accuracy significantly.
3 x Pt100 analog I/O
8
PTC sensor connected to digital input DI6 (see the
connection diagram on page
).
Note: Either 0 ohm (normal temperature) or 4000 ohm
(excessive temperature) will be shown by
. By default, an excessive temperature
will generate a warning as per parameter
. If you want a fault instead,
set
35.22 Temperature 2 fault limit
to 4000 ohm.
PTC DI6
20
PTC sensor connected to a standard analog input
selected by parameter
and an analog output. The input and output can be on
the drive control unit or on an extension module.
The required settings are the same as with selection
, except that the source selection
parameter of the analog output must be set to
.
PTC analog I/O
9
PTC sensor connected to encoder interface 1.
See also parameters
91.21 Module 1 temp sensor type
and
91.22 Module 1 temp filter time
PTC encoder module
1
10
PTC sensor connected to encoder interface 2.
See also parameters
91.24 Module 2 temp sensor type
and
91.25 Module 2 temp filter time
PTC encoder module
2
11
The temperature is taken from the source selected by
parameter
. The value of
the source is assumed to be in the unit of temperature
specified by
Direct temperature
13
Pt1000 sensor connected to a standard analog input
selected by parameter
and an analog output. The input and output can be on
the drive control unit or on an extension module.
The required settings are the same as with selection
, except that the source selection
parameter of the analog output must be set to
.
1 x Pt1000 analog
I/O
14
As selection
, but with two sensors
connected in series. Using multiple sensors improves
measurement accuracy significantly.
2 x Pt1000 analog
I/O
346 Parameters
Содержание ACS880 N5700 Series
Страница 1: ... ABB INDUSTRIAL DRIVES ACS880 position control program N5700 Firmware manual ...
Страница 2: ......
Страница 4: ......
Страница 22: ...22 ...
Страница 28: ...28 ...
Страница 32: ...32 ...
Страница 60: ...60 ...
Страница 456: ...Def Type FbEq 16b 32b Description Name Range Selection No 100 1 1 1 Overriding value 0 001 100 000 456 Parameters ...
Страница 546: ...546 ...
Страница 604: ...604 ...
Страница 626: ...626 ...
Страница 640: ...640 ...
Страница 660: ...660 ...