
The scaled references are shown by parameters
and
■
Actual values
Actual values are 16-bit words containing information on the operation of the
drive. The types of the monitored signals are selected by parameters
and
.
Debugging the network words
If parameter
is set to
, the actual values sent to the
fieldbus are displayed by
and
Scaling of actual values
Note: The scalings described below are for the ABB Drives communication profile.
Fieldbus-specific communication profiles may use different scalings. For more
information, see the manual of the fieldbus adapter.
The actual values are scaled as defined by parameters
...
; which scaling
is in use depends on the setting of parameters
and
Fieldbus
Drive
20000
10000
0
-10000
-20000
46.01 (with speed reference)
46.02 (with frequency reference)
46.03 (with torque reference)
46.04 (with power reference)
-(46.03) (with torque reference)
-(46.04) (with power reference)
-(46.01) (with speed reference)
-(46.02) (with frequency reference)
0
632 Fieldbus control through a fieldbus adapter
Содержание ACS880 N5700 Series
Страница 1: ... ABB INDUSTRIAL DRIVES ACS880 position control program N5700 Firmware manual ...
Страница 2: ......
Страница 4: ......
Страница 22: ...22 ...
Страница 28: ...28 ...
Страница 32: ...32 ...
Страница 60: ...60 ...
Страница 456: ...Def Type FbEq 16b 32b Description Name Range Selection No 100 1 1 1 Overriding value 0 001 100 000 456 Parameters ...
Страница 546: ...546 ...
Страница 604: ...604 ...
Страница 626: ...626 ...
Страница 640: ...640 ...
Страница 660: ...660 ...