Def / Type
FbEq 16b / 32b
Description
Name / Range /
Selection
No.
Mode 0 / uint16
Defines the mapping between parameters and holding
registers in the 400101…465535 Modbus register range.
Changes to this parameter take effect after the control
unit is rebooted or the new settings validated by
parameter
.
Addressing mode
58.33
0
16-bit values (groups 1…99, indexes 1…99):
Register address = 100 × parameter group
+ parameter index. For example, parameter 22.80 would
be mapped to register 2200 + 80 = 402280.
32-bit values (groups 1…99, indexes 1…99):
Register address = 200 × parameter group
+ 2 × parameter index. For example, parameter 22.80
would be mapped to register 4400 + 160 =
424560.
Mode 0
1
16-bit values (groups 1…255, indexes 1…255):
Register address = 256 × parameter group
+ parameter index. For example, parameter 22.80 would
be mapped to register 5632 + 80 = 405712.
Mode 1
2
32-bit values (groups 1…127, indexes 1…255):
Register address = 512 × parameter group +
2 × parameter index. For example, parameter 22.80
would be mapped to register 11264 + 160 =
411424.
Mode 2
LO-HI / uint16
Selects in which order 16-bit registers of 32-bit
parameters are transferred.
For each register, the first byte contains the high order
byte and the second byte contains the low order byte.
Changes to this parameter take effect after the control
unit is rebooted or the new settings validated by
parameter
.
Word order
58.34
0
The first register contains the high order word, the
second contains the low order word.
HI-LO
1
The first register contains the low order word, the
second contains the high order word.
LO-HI
- / uint16
Activates fieldbus communication monitoring
separately for each control location (see section
control vs. external control (page 23)
).
The parameter is primarily intended for monitoring the
communication with EFB when it is connected to the
application program and not selected as a control
source by drive parameters.
EFB comm
supervision force
58.36
1 = Communication monitoring active when Ext 1 is
being used.
Ext 1
b0
1 = Communication monitoring active when Ext 2 is
being used.
Ext 2
b1
1 = Communication monitoring active when local
control is being used.
Local
b2
Reserved
b3…15
1 = 1
0000h…FFFFh
402 Parameters
Содержание ACS880 N5700 Series
Страница 1: ... ABB INDUSTRIAL DRIVES ACS880 position control program N5700 Firmware manual ...
Страница 2: ......
Страница 4: ......
Страница 22: ...22 ...
Страница 28: ...28 ...
Страница 32: ...32 ...
Страница 60: ...60 ...
Страница 456: ...Def Type FbEq 16b 32b Description Name Range Selection No 100 1 1 1 Overriding value 0 001 100 000 456 Parameters ...
Страница 546: ...546 ...
Страница 604: ...604 ...
Страница 626: ...626 ...
Страница 640: ...640 ...
Страница 660: ...660 ...