Def / Type
FbEq 16b / 32b
Description
Name / Range /
Selection
No.
12
Bit 2 of
74.7 User Position control word 1
.
User Position CW1
bit 2
13
Bit 3 of
74.7 User Position control word 1
.
User Position CW1
bit 3
14
Bit 4 of
74.7 User Position control word 1
User Position CW1
bit 4
15
Bit 5 of
74.7 User Position control word 1
.
User Position CW1
bit 5
16
Bit 6 of
74.7 User Position control word 1
User Position CW1
bit 6
17
Bit 7 of
74.7 User Position control word 1
User Position CW1
bit 7
0.000 units / real32
Defines the expected latch position from axis shaft.
Axis latch position
78.11
1000 = 1 units / 1 = 1
units
Latch position from axis shaft.
-2000000.000 ...
2000000.000 units
0.000 units / real32
Defines the expected latch axis shaft position from the
master shaft probe.
Master latch
position
78.12
1000 = 1 units / 1 = 1
units
Latch axis shaft position from the master shaft probe.
-2000000.000 ...
2000000.000 units
0.000 units / real32
Defines the minimum threshold for the cyclic
correction. For example, if the minimum value is set to
30 degrees and the requested cyclic correction is 20
degrees, no correction is made.
Minimum correction
78.13
1000 = 1 units / 1 = 1
units
Minimum threshold for the cyclic correction.
0.000 ...
2000000.000 units
0.000 units / real32
Defines the maximum threshold for cyclic correction.
For example, if the maximum value is set to 50 degrees
and the requested cyclic correction is 60 degrees, no
correction is made.
Maximum correction
78.14
1000 = 1 units / 1 = 1
units
Maximum threshold for cyclic correction.
0.000 ...
2000000.000 units
0.000 units / real32
Defines the maximum correction value that can be
applied anytime after the first cyclic correction. This
can be used to calm down corrections in case there is
a jitter in the measurement. For example, if maximum
single correction value defined is 10 degrees and the
maximum cyclic correction value is 30 degrees, only 10
degrees is corrected at one cycle.
Maximum single
correction
78.15
1000 = 1 units / 1 = 1
units
Maximum correction value after the initial cyclic
correction.
0.000 ...
2000000.000 units
Parameters 461
Содержание ACS880 N5700 Series
Страница 1: ... ABB INDUSTRIAL DRIVES ACS880 position control program N5700 Firmware manual ...
Страница 2: ......
Страница 4: ......
Страница 22: ...22 ...
Страница 28: ...28 ...
Страница 32: ...32 ...
Страница 60: ...60 ...
Страница 456: ...Def Type FbEq 16b 32b Description Name Range Selection No 100 1 1 1 Overriding value 0 001 100 000 456 Parameters ...
Страница 546: ...546 ...
Страница 604: ...604 ...
Страница 626: ...626 ...
Страница 640: ...640 ...
Страница 660: ...660 ...