Def / Type
FbEq 16b / 32b
Description
Name / Range /
Selection
No.
- / uint16
Activates master/follower communication monitoring
separately for each control location (see section
control vs. external control (page 23)
).
The parameter is primarily intended for monitoring the
communication with master or follower when it is
connected to the application program and not selected
as a control source by drive parameters.
M/F comm
supervision force
60.32
1 = Communication monitoring active when Ext 1 is
being used.
Ext 1
b0
1 = Communication monitoring active when Ext 2 is
being used.
Ext 2
b1
1 = Communication monitoring active when local
control is being used.
Local
b2
Reserved
b3…15
1 = 1
0000h…FFFFh
Not in use / uint16
Enables/disables the use of a fast time level on the
master/follower communication link. If the
master/follower functionality is used for position
control, the parameter must be set to
in both
the master and the follower drives.
Fast M/F comm
mode
60.33
0
Faster time level disabled.
Disabled
1
Faster time level enabled.
Enable
Not in use / uint16
Selects the channel used for connecting an optional
FEA-xx extension adapter.
Extension adapter
com port
60.41
0
None (communication disabled).
Not in use
1
Channel A on FDCO module in slot 1.
Slot 1A
2
Channel A on FDCO module in slot 2.
Slot 2A
3
Channel A on FDCO module in slot 3.
Slot 3A
4
Channel B on FDCO module in slot 1.
Slot 1B
5
Channel B on FDCO module in slot 2.
Slot 2B
6
Channel B on FDCO module in slot 3.
Slot 3B
13
Channel CH 3 on RDCO module (with BCU control unit
only).
ABB engineered drive
/ uint16
In ModuleBus communication, defines whether the
drive is of the “engineered” or “standard” type.
Note: This parameter cannot be changed while the
drive is running.
DDCS controller
drive type
60.50
0
The drive is an “engineered drive” (data sets 10…25 are
used).
ABB engineered
drive
1
The drive is a “standard drive” (data sets 1…4 are used).
ABB standard drive
Not in use / uint16
Selects the DDCS channel used for connecting an
external controller (such as an AC 800M).
DDCS controller
comm port
60.51
0
None (communication disabled).
Not in use
416 Parameters
Содержание ACS880 N5700 Series
Страница 1: ... ABB INDUSTRIAL DRIVES ACS880 position control program N5700 Firmware manual ...
Страница 2: ......
Страница 4: ......
Страница 22: ...22 ...
Страница 28: ...28 ...
Страница 32: ...32 ...
Страница 60: ...60 ...
Страница 456: ...Def Type FbEq 16b 32b Description Name Range Selection No 100 1 1 1 Overriding value 0 001 100 000 456 Parameters ...
Страница 546: ...546 ...
Страница 604: ...604 ...
Страница 626: ...626 ...
Страница 640: ...640 ...
Страница 660: ...660 ...