Def / Type
FbEq 16b / 32b
Description
Name / Range /
Selection
No.
Disabled / uint16
Selects the source from which measured temperature
2 is read.
For wiring examples, see the hardware manual of the
drive.
Usually this source is from a sensor connected to the
motor controlled by the drive, but it could be used to
measure and monitor a temperature from other parts
of the process as long as a suitable sensor is used as
per the selection list.
Temperature 2
source
35.21
0
None. Temperature monitoring function 2 is disabled.
Disabled
1
Estimated motor temperature (see parameter
).
The temperature is estimated from an internal drive
calculation. It is important to set up the ambient
temperature of the motor in
Estimated
temperature
2
KTY84 sensor connected to the analog input selected
by parameter
and an
analog output. The input and output can be on the drive
control unit or on an extension module.
The following settings are required:
•
Set the hardware jumper or switch related to the
analog input to U (voltage). Any change must be
validated by a control unit reboot.
•
Set the unit selection parameter of the input to
volt.
•
Set the source selection parameter of the analog
output to “
•
Select the analog input in parameter
. In case
the input is located on an I/O extension module,
use the selection Other (see
) to point at the actual
input value parameter (for example,
The analog output feeds a constant current through
the sensor. As the resistance of the sensor changes
along with its temperature, the voltage over the sensor
changes. The voltage is read by the analog input and
converted into degrees.
KTY84 analog I/O
3
KTY84 sensor connected to encoder interface 1.
See also parameters
91.21 Module 1 temp sensor type
and
91.22 Module 1 temp filter time
.
KTY84 encoder
module 1
4
KTY84 sensor connected to encoder interface 2.
See also parameters
91.24 Module 2 temp sensor type
and
91.25 Module 2 temp filter time
.
KTY84 encoder
module 2
Parameters 345
Содержание ACS880 N5700 Series
Страница 1: ... ABB INDUSTRIAL DRIVES ACS880 position control program N5700 Firmware manual ...
Страница 2: ......
Страница 4: ......
Страница 22: ...22 ...
Страница 28: ...28 ...
Страница 32: ...32 ...
Страница 60: ...60 ...
Страница 456: ...Def Type FbEq 16b 32b Description Name Range Selection No 100 1 1 1 Overriding value 0 001 100 000 456 Parameters ...
Страница 546: ...546 ...
Страница 604: ...604 ...
Страница 626: ...626 ...
Страница 640: ...640 ...
Страница 660: ...660 ...