Def / Type
FbEq 16b / 32b
Description
Name / Range /
Selection
No.
Not selected / uint32
When parameter
is set to
or
, this parameter selects the
source of actual value 2 transmitted to the fieldbus
network through fieldbus adapter B.
FBA B act2
transparent source
50.41
0
No source selected.
Not selected
See
Terms and abbreviations (page 130)
Other [value]
Disable / uint16
Enables the display of raw (unmodified) data received
from and sent to fieldbus adapter B in parameters
This functionality should only be used for debugging.
Note: This parameter cannot be changed while the
drive is running.
FBA B debug mode
50.42
0
Display of raw data from fieldbus adapter B disabled.
Disable
1
Display of raw data from fieldbus adapter B enabled.
Fast
0 / uint32
Displays the raw (unmodified) control word sent by the
master (PLC) to fieldbus adapter B if debugging is
enabled by parameter
.
This parameter is read-only.
FBA B control word
50.43
1 = 1
Control word sent by master to fieldbus adapter B.
00000000…FFFFFFFFh
- / int32
Displays raw (unmodified) reference REF1 sent by the
master (PLC) to fieldbus adapter B if debugging is
enabled by parameter
.
This parameter is read-only.
FBA B reference 1
50.44
- / int32
Displays raw (unmodified) reference REF2 sent by the
master (PLC) to fieldbus adapter B if debugging is
enabled by parameter
.
This parameter is read-only.
FBA B reference 2
50.45
0 / uint32
Displays the raw (unmodified) status word sent by
fieldbus adapter B to the master (PLC) if debugging is
enabled by parameter
.
This parameter is read-only.
FBA B status word
50.46
1 = 1
Status word sent by fieldbus adapter B to master.
00000000…FFFFFFFFh
- / int32
Displays raw (unmodified) actual value ACT1 sent by
fieldbus adapter B to the master (PLC) if debugging is
enabled by parameter
.
This parameter is read-only.
FBA B actual value 1
50.47
- / int32
Displays raw (unmodified) actual value ACT2 sent by
fieldbus adapter B to the master (PLC) if debugging is
enabled by parameter
.
This parameter is read-only.
FBA B actual value 2
50.48
386 Parameters
Содержание ACS880 N5700 Series
Страница 1: ... ABB INDUSTRIAL DRIVES ACS880 position control program N5700 Firmware manual ...
Страница 2: ......
Страница 4: ......
Страница 22: ...22 ...
Страница 28: ...28 ...
Страница 32: ...32 ...
Страница 60: ...60 ...
Страница 456: ...Def Type FbEq 16b 32b Description Name Range Selection No 100 1 1 1 Overriding value 0 001 100 000 456 Parameters ...
Страница 546: ...546 ...
Страница 604: ...604 ...
Страница 626: ...626 ...
Страница 640: ...640 ...
Страница 660: ...660 ...