Def / Type
FbEq 16b / 32b
Description
Name / Range /
Selection
No.
Enable / uint16
(Only visible with a BCU control unit)
Activates communication to a BSFC charging controller.
This setting is intended for use with inverter modules
that are connected to a DC bus through a DC
switch/charging circuit controlled by a charging
controller. On units without a DC switch, this parameter
should be set to
.
The charging controller monitors the charging of the
inverter unit, and sends an enable command when the
charging has finished (ie. DC switch is closed after the
'charging OK' lamp lights, and charging switch opened).
For more information, see BSFC documentation.
Switch fuse
controller
95.9
0
Communication with BSFC disabled.
1
Communication with BSFC enabled.
- / uint16
(Only visible with BCU control unit)
Specifies which converter modules have been removed
from the converter configuration. A value other than 0
activates the reduced run function.
See section
Reduced run function (page 124)
.
Reduced run mask
95.12
Module 1 has been removed.
Module 1 removed
b0
Module 2 has been removed.
Module 2 removed
b1
Module 3 has been removed.
Module 3 removed
b2
Module 4 has been removed.
Module 4 removed
b3
Module 5 has been removed.
Module 5 removed
b4
Module 6 has been removed.
Module 6 removed
b5
Module 7 has been removed.
Module 7 removed
b6
Module 8 has been removed.
Module 8 removed
b7
Module 9 has been removed.
Module 9 removed
b8
Module 10 has been removed.
Module 10 removed
b9
Module 11 has been removed.
Module 11 removed
b10
Module 12 has been removed.
Module 12 removed
b11
Reserved
b12…15
1 = 1
0000h…FFFFh
- / uint16
(Only visible with a BCU control unit)
Specifies the number of inverter modules available.
This parameter must be set if reduced run is required.
A value other than 0 activates the reduced run function.
If the control program cannot detect the number of
modules specified by this parameter, a fault (
) is generated.
See section
Reduced run function (page 124)
.
0 = Reduced run disabled
1…12 = Number of modules available
Note: This parameter cannot be changed while the
drive is running.
Reduced run mode
95.13
510 Parameters
Содержание ACS880 N5700 Series
Страница 1: ... ABB INDUSTRIAL DRIVES ACS880 position control program N5700 Firmware manual ...
Страница 2: ......
Страница 4: ......
Страница 22: ...22 ...
Страница 28: ...28 ...
Страница 32: ...32 ...
Страница 60: ...60 ...
Страница 456: ...Def Type FbEq 16b 32b Description Name Range Selection No 100 1 1 1 Overriding value 0 001 100 000 456 Parameters ...
Страница 546: ...546 ...
Страница 604: ...604 ...
Страница 626: ...626 ...
Страница 640: ...640 ...
Страница 660: ...660 ...