Def / Type
FbEq 16b / 32b
Description
Name / Range /
Selection
No.
15
As selection
, but with three
sensors connected in series. Using multiple sensors
improves measurement accuracy significantly.
3 x Pt1000 analog
I/O
16
Pt1000 sensor connected to encoder interface 1. See
parameters
91.21 Module 1 temp sensor type
and
Note: Pt1000 sensor is supported with FEN-11 and
FEN-31 encoder modules only.
Pt1000 encoder
module 1
17
Pt1000 sensor connected to encoder interface 2. See
parameters
91.24 Module 2 temp sensor type
and
.
Note: Pt1000 sensor is supported with FEN-11 and
FEN-31 encoder modules only.
Pt1000 encoder
module 2
130 ° / real32
Defines the fault limit for temperature monitoring
function 2.
When measured temperature 2 exceeds the limit, the
drive trips on fault
The unit is selected by parameter
.
Note: With °F, the range is -76…1832. With a PTC sensor,
the range is 0…5000 ohms.
Temperature 2 fault
limit
35.22
1 = 1 ° / 1 = 1 °
Fault limit for temperature monitoring function 2.
-60...1000 °
110 ° / real32
Defines the warning limit for temperature monitoring
function 2. When measured temperature 2 exceeds the
limit, a warning
(
) is generated.
The unit is selected by parameter
.
Note: With °F, the range is -76…1832. With a PTC sensor,
the range is 0…5000 ohms.
Temperature 2
warning limit
35.23
1 = 1 ° / 1 = 1 °
Warning limit for temperature monitoring function 2.
-60...1000 °
Not selected / uint32
Selects the input for parameter
, selections
,
,
and
.
Temperature 2 AI
source
35.24
0
None.
Not selected
1
Analog input AI1 on the control unit.
AI1 actual value
2
Analog input AI2 on the control unit.
AI2 actual value
See
Terms and abbreviations (page 130)
.
Other [value]
0 °C / real32
Defines the calibration of temperature 2.
See parameter
35.17 Temperature 1 calibration
.
Temperature 2
calibration
35.27
1 = 1 °C / 1 = 1 °C
Calibration of temperature 2 in celsius.
-30...1000 °C
- / uint16
Activates FPTC-xx thermistor protection modules
installed on the control unit of the drive. Using this
word, it is also possible to suppress the warnings (but
not faults) from each module.
FPTC configuration
word
35.30
1 = Yes: Module installed in slot 1.
Module in slot 1
b0
Parameters 347
Содержание ACS880 N5700 Series
Страница 1: ... ABB INDUSTRIAL DRIVES ACS880 position control program N5700 Firmware manual ...
Страница 2: ......
Страница 4: ......
Страница 22: ...22 ...
Страница 28: ...28 ...
Страница 32: ...32 ...
Страница 60: ...60 ...
Страница 456: ...Def Type FbEq 16b 32b Description Name Range Selection No 100 1 1 1 Overriding value 0 001 100 000 456 Parameters ...
Страница 546: ...546 ...
Страница 604: ...604 ...
Страница 626: ...626 ...
Страница 640: ...640 ...
Страница 660: ...660 ...