Def / Type
FbEq 16b / 32b
Description
Name / Range /
Selection
No.
3 / uint16
Specifies the slot (1…3) on the control unit of the drive
into which the interface module is installed.
Alternatively, specifies the node ID of the slot on an
FEA-03 extension adapter.
Module 2 location
91.14
1 = 1 / 1 = 1
Slot 1 = 1; Slot 2 = 2; Slot 3 = 3
4…254: Node ID of the slot on the FEA-03 extension
adapter
1...254
None / uint16
Specifies the type of temperature sensor connected
to interface module 1. Note that the module must also
be activated by parameters
…
Module 1 temp
sensor type
91.21
0
None.
None
1
PTC. (The unit is ohms.)
PTC
2
KTY84. (The unit is selected by parameter
KTY-84
3
Pt1000 (The unit is selected by parameter
Note: Pt1000 sensor supports FEN-11 and FEN-31
encoder modules only.
Pt1000
1500 ms / real32
Defines a filtering time for the temperature
measurement through interface module 1.
Module 1 temp filter
time
91.22
- / -
Filtering time for temperature measurement.
0...10000 ms
None / uint16
Specifies the type of temperature sensor connected
to interface module 2. Note that the module must also
be activated by parameters
…
.
Module 2 temp
sensor type
91.24
0
None.
None
1
PTC. (The unit is ohms.)
PTC
2
KTY84. (The unit is selected by parameter
KTY-84
3
Pt1000 (The unit is selected by parameter
Note: Pt1000 sensor supports FEN-11 and FEN-31
encoder modules only.
Pt1000
1500 ms / real32
Defines a filtering time for the temperature
measurement through interface 2.
Module 2 temp filter
time
91.25
- / -
Filtering time for temperature measurement.
0...10000 ms
Not selected / uint16
Selects the encoder input on interface module 1 whose
signal is echoed by or emulated to the TTL output.
See also section
.
Module 1 TTL output
source
91.31
0
TTL output not in use.
Not selected
1
Input 1 is echoed by or emulated to the TTL output.
Module input 1
2
Input 2 is echoed by or emulated to the TTL output.
Module input 2
- / uint16
Defines the number of TTL pulses per revolution for
encoder emulation output of interface module 1.
Module 1 emulation
pulses/rev
91.32
1 = 1 / 1 = 1
Number of TTL pulses for emulation.
0...65535
Parameters 491
Содержание ACS880 N5700 Series
Страница 1: ... ABB INDUSTRIAL DRIVES ACS880 position control program N5700 Firmware manual ...
Страница 2: ......
Страница 4: ......
Страница 22: ...22 ...
Страница 28: ...28 ...
Страница 32: ...32 ...
Страница 60: ...60 ...
Страница 456: ...Def Type FbEq 16b 32b Description Name Range Selection No 100 1 1 1 Overriding value 0 001 100 000 456 Parameters ...
Страница 546: ...546 ...
Страница 604: ...604 ...
Страница 626: ...626 ...
Страница 640: ...640 ...
Страница 660: ...660 ...