SECTION 3 - MICROBOARD 031-01730-000
FORM 160.54-M1
ISSUE DATE: 10/25/2019
JOHNSON CONTROLS
JCI COMPANY CONFIDENTIAL
3
FIGURE 15 -
CONFIGURABLE ANALOG AND REMOTE SETPOINT INPUTS
LD09565
NOTE:
1. Program Jumpers JP23 – JP24 must be positioned on pins 1-2 or 3-4 according to input signal type.
2. Applies to Flash memory card version C.MLM.01.07.xxx and later. Program Jumpers JP21 and JP22 must be on pins 2-3 on style F and
later chillers equipped with factory-mounted thermal-type flow sensors.
FACTORY MOUNTED EVAPORATOR
THERMAL-TYPE FLOW SENSOR
(style F and later chillers) (note 2)
REMOTE CURRENT
LIMIT SETPOINT
REMOTE LEAVING
CHILLED LIQUID
TEMP SETPOINT
REMOTE SETPOINT
GND CONNECTIONS
24 VAC
0-10 VDC /
2-10 VDC
0-20 mA /
4-20 mA
5
4
3
1
2
16
4
14
2
4
2
13
15
1
3
MUX
47K
JP21
JP22
JP23
JP24
200
7.5 K
1
2
3
1
2
3
1
2
3
1
2
3
71.5 K
+5V
3
17
+5V
J7
J22
0-10 VDC /
2-10 VDC
0-20 mA /
4-20 mA
FACTORY MOUNTED CONDENSER
THERMAL-TYPE FLOW SENSOR
(style F and later chillers) (note 2)
24 VAC
2
4
1
3