344
FORM 160.54-M1
ISSUE DATE: 10/25/2019
SECTION 36 - SOFTWARE ENHANCEMENTS
JCI COMPANY CONFIDENTIAL
JOHNSON CONTROLS
The calibration procedure can be termi-
nated at any time during the procedure
by pressing the CANCEL CALIB key.
If the PRVs were previously calibrated
successfully, they will revert to using the
previous calibration values. If they were
not previously calibrated successfully,
they will remain uncalibrated.
VSD ADAPTIVE CAPACITY CONTROL -
STABILITY LIMIT SETPOINT
This compressor motor VSD setpoint default is now
7000 (was 4500).
E-LINK GATEWAY INDUCED REBOOTS
With previous flash memory card versions, E-Link Gate-
way communications could cause the microboard to ran-
domly reboot was corrected in this version.
SI0080 - SOFTWARE ENHANCEMENTS EFFECTIVE JANUARY 2004 (CONT'D)