SI0265 - SOFTWARE ENHANCEMENTS (VER 24) EFFECTIVE MAY 2012 (CONT'D)
This warning will automatically reset whenever
the chiller is running or the Saturated Condenser
Temperature is > 40.0 °F or the Condenser Flow
Switch closes.
Diagnostics - Analog Screen
Text has been added next to all the used input channels
to make it easier to understand what inputs are associ-
ated to what voltage.
Diagnostics - Digital Screen
Low Voltage Digital Inputs J14-1, J14-4, J14-7 and J14-
10 were added to the Digital Inputs Diagnostic screen.
J14-1 = Chilled Liquid Thermal-Type flow switch.
J14-7 = Condenser Liquid Thermal-Type flow switch,
and J14-10 Heat Recovery Condenser Liquid Thermal-
Type flow switch.
Sales Order Data Upload
The factory sales order upload port was moved from
COM2 to COM4b.
Surge Avoidance Surge Sensitivity
The Surge Avoidance Surge Sensitivity previously up-
dated changes only on power up. This has now been
enhanced to immediately update any changes to Surge
Avoidance Surge Sensitivity when they are entered.
Anti-Recycle Start Inhibit
The Anti-Recycle Start Inhibit did not work properly in
V17 through V23 after any immediate shutdown Cy-
cling Fault. This start inhibit feature has been corrected
to function properly.
Heat Pump Duty
The Heat Pump Duty enable on the Setup Screen is
selectable in Test Op Access Level and above when the
refrigerant is R134a.
Graphics Library - Selection Box Wraparound
An enhancement has been added to allow the green se-
lection box to wrap around when scrolling through a
list of programmable items. For example, when scroll-
ing through the programmable settings on the Setup
Screen, when pressing the down arrow while on the
bottom item, the green box will move to the top item.
Password Field Clear on Failure
Add a feature to automatically clear the password field
on a re-prompt after a password entry failure.
Run Time Precision in Reports
A Seconds field has been added to the Run Time in the
History and Status Reports to allow better fault event
correlation
PC Printer Type
A new selection for Printer Type called PC has been
added. When PC is selected, the time delays required
for the printers have been removed allowing printing
reports to a PC to be much faster than printing to a
printer.
Language Enhancements
Russian –
The Russian Language has been added as a
standard language selection
Japanese
1. Evaporator Screen – Corrected the font sizing on
this screen
2. Condenser Screen – Corrected the font sizing