109
SECTION 7 - LIQUID CRYSTAL DISPLAY
FORM 160.54-M1
ISSUE DATE: 10/25/2019
JOHNSON CONTROLS
JCI COMPANY CONFIDENTIAL
7
result of that same agreement. Therefore, the Display
received for service replacement may be by a differ-
ent manufacturer than the one in the OptiView Control
Center. Since each Display manufacturer requires a
specific Display Interface Board, Backlight and Back-
light Ribbon Cable, replacement Displays are ordered
and supplied as a Display Replacement Kit (YORK
Part Number 331-01771-000) to ensure component
compatibility. The items supplied in the kit are compat-
ible with the supplied Display. Display Replacement
Kit 331-01771-000 consists of the following items
mounted on a display mounting plate:
1. Liquid Crystal Display with Lamp
2. Appropriate Display Interface Board for item 1
3. Appropriate Backlight Inverter Board for item 1
4. Appropriate ribbon cable (Backlight Inverter
Board to Microboard) for item 1
5. Ribbon cable (Display Interface Board to
Microboard)
6. All mounting hardware
7. Installation instructions. A label attached to the
display mounting plate lists the YORK part
numbers of the Display supporting components
mounted on the display mounting plate and the re-
quired Microboard Program Jumper (JP2 through
8) configurations. Microboard Program Jumpers
JP2 through
JP8 will have to be configured appro
-
priately for the replacement display.
Display Handling
1. The display is made of glass. It could break if
dropped.
2. The display front surface is easily scratched. If
soiled, wipe with a dry cotton cloth. Use no water
or chemicals.
3. The display is static sensitive. Electrostatic dis-
charges may damage the display.
4.
A laminated film is adhered to the display front
glass surface to prevent it from being scratched.
Peel off very slowly to prevent static damage.
Always remove control power from the
OptiView Control Center before connect-
ing or disconnecting wires to the display.
Connecting or disconnecting wires to the
display with power applied will damage
the display.
BACKLIGHT LAMP REPLACEMENT
SHARP LQ10D367/368 (031-01774-000) Display
Removal
The Lamp slides into the Display from left to right and
is secured with a locking tab. See
111.
1. Remove control power from the OptiView Con-
trol Center.
2. Remove protective cover from rear of Display.
3. Disconnect lamp AC power connector from Back-
light Inverter Board.
4.
Using fingernail or thin flat blade screwdriver,
bend the locking tab outward slightly to clear the
lamp housing protrusion.
5. Grasp lamp AC power connector and gently pull
until lamp housing clears locking tab.
6. Grasp lamp housing and pull until lamp housing is
completely removed from the Display.
Installation
1. Slide new lamp into Display from left to right
until lamp housing protrusion locks into Display
locking tab.
2. Connect lamp AC power connector to Backlight
Inverter Board.
3. Apply control power to OptiView Control Center.
LG Semicon LP104V2-W (031-02046-000) and
SHARP LQ104V1DG61 (031-02886-000) Display
Removal
The lamp slides into the Display from left to right and is
secured with a screw. See
.
1. Remove control power from the OptiView Con-
trol Center.
2. Remove protective cover from rear of Display.
3. Disconnect lamp AC power connector from Back-
light Inverter Board.
4. Using small Phillips screwdriver, remove lamp
retaining screw.
5. Grasp lamp AC power connector and gently pull
until lamp housing is completely removed from
the Display.