SECTION 33 - SYSTEM CALIBRATION, SERVICE SETPOINTS, AND RESET PROCEDURES
JCI COMPANY CONFIDENTIAL
JOHNSON CONTROLS
When using this password to enter data
into a new blank BRAM, the FINISH
PANEL SETUP procedure (listed at the
end of the entry procedure below) must be
performed after all data has been entered.
Failure to perform this procedure will re-
sult in unreliable OptiView Control Center
operation! If this procedure is performed
before entering all data, the ability to enter
more data will be terminated.
Use the following procedure to enter data:
1. At the keypad, log in at the appropriate access
level to change the desired values.
2. From the SETPOINTS Screen, select SETUP
SCREEN. From the SETUP Screen, select SALES
ORDER Screen.
3. If logged in at SERVICE access level, press SET
ORDER INFO key to enter Commissioning date,
Job Name or Location and proceed to step 4. If
logged in at ADMIN or Test Op level, Press SE-
LECT key to select the data category (ORDER, DE-
SIGN, NAMEPLATE, SYSTEM) to be entered.
4.
Press CHANGE key. The first changeable area in
the selected category will be outlined in a green se-
lection box. The procedure can be terminated any-
time after this by pressing the CANCEL (x) key.
5.
Use the ▲ and ▼ keys to move the green selec
-
tion box to the desired value to be changed, within
the category selected.
6. Press ENTER (
) key.
7. Enter the appropriate data. Use the numeric key-
pad keys to enter numbers. Use the • key to enter
a decimal point. Use the ▲ and ▼ keys to scroll
sequentially up and down through the alphabet
to enter letters or a comma (,), slash (/) or minus
sign (-). Each time the ▲ key is pressed, the next
higher sequential alphabet letter is displayed.
Each time the ▼ key is pressed, the next lower
alphabet letter is displayed. The comma, slash and
minus sign can be selected after scrolling through
the entire alphabet. During the entry process, the
◄ key can be used to backspace and the ► key
can be used to forward space.
8. Press ENTER (
) key.
9.
Use ▲ and ▼ keys to select another value to be
changed within the same category or press CAN-
CEL (X) key to exit and allow selection of another
category.
10.
Extremely Important!
If the procedure above
was performed using password 0 2 2 8 to enter
data into a new blank BRAM, the following pro-
cedure must be performed after all the desired
data is entered. If the following procedure is per-
formed before entering all of the data, the ability
to enter more data will be terminated. Failure to
perform this procedure after all data has been en-
tered will result in unreliable OptiView Control
Center Operation!
a. On SALES ORDER screen, press FINISH
PANEL SETUP key.
b. Use
◄
and
►
key to select YES.
c. Press ENTER (
) key.
CUSTOM USER ID AND PASSWORDS
When logging in, the user is requested to enter a User
ID, followed by a Password. The universal and Default
User ID is zero (0). The universal Password to log in
at OPERATOR access level is 9 6 7 5. The universal
Password to log in at SERVICE access level is 1 3 8 0.
No log in is required for VIEW access level. However,
if desired, the Service technician can establish up to
four custom User ID’s and Passwords that can be used
by Operations personnel to log in at VIEW, OPERA-
TOR, or SERVICE level.
Up to four Custom Users can be established with User
ID’s from 1 to 9999. Each user can be assigned a Pass-
word of 0 to 9999 and an access level of VIEW, OP-
ERATOR or SERVICE.
Use the following procedure to establish Custom
Users:
1. At the keypad, log in at SERVICE access level
using 1 3 8 0.
2. From the SETPOINTS Screen, select SETUP
Screen. From SETUP Screen, select USER
Screen.
3. Press CHANGE USER ATTRIBUTES key. The
first changeable area is outlined in a green selec
-
tion box.
4. Use the
◄
,
►
,
▲
or
▼
keys to move the green
selection box to the desired value to be changed.