SECTION 35 - SYSTEM COMMISSIONING CHECKLIST
JCI COMPANY CONFIDENTIAL
JOHNSON CONTROLS
MOTOR Screen (MV VSD)
____ Full Load Amps
ADAPTIVE CAPACITY CONTROL (ACC)
DETAILS Screen
____ Surge Map Clear
____ Surge Map Print
____ Auto Map Print
____ Surge Margin Adjust
____ Auto Map Print (Modbus Protocol configu-
ration; software version C.OPT.01.18.307
and later)
____
Surge Sensitivity (software version
C.OPT..01.21.307 and later)
____ Manual Surge Point
____ Mapping Enable (Modbus Protocol configu-
ration; software version C.OPT.01.21.307
and later)
____
VSD Start Frequency (Modbus Pro-
tocol configuration; software version
C.OPT.01.21.307 and later)
MOTOR LUBRICATION
Screen
____
Enable/Disable Motor Auto Lubrication
(software version C.OPT.01.16.xxx (or lat-
er))
____
Enable/Disable the Motor Lubrication
Warning Safety Shutdown (if Motor Lube
is disabled) (software version C.OPT.01.16.
xxx (or later))
MOTOR DETAILS SCREEN
(Software version
C.OPT.01.22.307 and later)
____ Winding Temperature Protection
____ Bearing Temperature Protection
____ Motor Vibration Protection
____ Motor Cooling Coil Leak Protection
____ Manual Baseline or Auto Baseline
MOTOR SETPOINTS SCREEN
(Software version
C.OPT.01.22.307 and later)
____ Temperature Disable
____ Winding Setup
____ Vibration Setup
____ Vibration Gain
____ Bearing Setup
14.
SETPOINTS Screen
(160.54-O1)
With the exception of the “Remote Analog Input
Range”, the setpoints listed on the SETPOINTS
Screen have already been programmed above on
previous screens. The values shown reflect the
previously programmed values. However, the set-
points listed here can be changed on this screen if
desired. This screen is used primarily as a central
location from which most setpoints can be pro-
grammed. If it is not desired to change any of the
listed setpoints, proceed to the SETUP Screen be-
low.
____ Remote Analog Input Range
SETUP Screen
____ Enable clock
____ Enter clock time and date
____ Select 12- or 24-hour Display Mode
Microboard 031-01730-000:
____ The state of program jumpers/switches that
affect chiller operation are displayed. These
were configured in Step 1. Confirm they are
correct. (
Microboard 031-02430-000/-001, 031-03630-001:
____ The state of program switches SW1-1 (re-
frigerant selection) and SW1-2 (liquid type)
is displayed. These were configured in Step
1. Confirm they are correct. (
MICROBOARD 031-02430-000 AND 031-
02430-001 or SECTION 5- 031-03630-001
).
Enter the following setpoints: (160.54-M1)
____ Chilled Liquid Pump Operation
____ Motor Drive Type
____ Anti-Recycle
____ Power Failure Restart
____ Coastdown
____ Pre-run