18-32
IM 05P02C41-01EN
Output Setting Menu (Menu: OUT) (Continued from previous page)
Parameter
symbol
Name
Display
level
Setting range
Initial value
OU.H
100% segmental
point of OUT
current output
PRO
-100.0 to 200.0%
100.0%
OU.L
0% segmental point
of OUT current
output
PRO
0.0%
OU2.H
100% segmental
point of OUT2
current output
PRO
100.0%
OU2.L
0% segmental point
of OUT2 current
output
PRO
0.0%
RET.H
100% segmental
point of RET current
output
PRO
100.0%
RET.L
0% segmental point
of RET current
output
PRO
0.0%
OU.A
OUT current output
range
PRO
4-20: 4 to 20 mA
0-20: 0 to 20 mA
20-4: 20 to 4 mA
20-0: 20 to 0 mA
4-20
OU2.A
OUT2 current
output range
PRO
4-20
RET.A
RET current output
range
PRO
4-20
MAN.T
Manual output
operation type
PRO
Selects how to manipulate the
control output during manual
operation. (Note)
DT.ET: Direct key method
(The value specified by the Up
and Down arrow keys is output
as is.)
ST.ET: SET/ENT key method
(The value specified on the
setting display and confirmed
with the SET/ENT key is
output.)
DT.ET
Note: When the control type (CNT) is set to ON/OFF control, two-position two-level control or
heating/cooling control, only the DT.ET setting can be used. On the position proportional type,
parameter MAN.T does not appear.
Heater Break Alarm Setting Menu (Menu: HBA)
Parameter
symbol
Name
Display
level
Setting range
Initial value
HB1.S,
HB2.S
Heater break
alarm-1, -2 function
selection
EASY
0: Heater current measurement
1: Heater break alarm
1
HB1, HB2
Heater break
alarm-1, -2 current
setpoint
EASY
OFF, 0.1 to 300.0 Arms
OFF
CT1.T, CT2.T
CT1, CT2 coil
winding number
ratio
EASY
1 to 3300
800
HDN1, HDN2
Heater break
alarm-1, -2 On-
delay timer
STD
0.00 to 99.59 (minute.second)
0.00
HDF1, HDF2
Heater break
alarm-1, -2 Off-
delay timer
PRO
0.00
HB1.D,
HB2.D
Heater break
alarm-1, -2 contact
type
PRO
CLS: When the event occurs, the
contact is closed.
OPN: When the event occurs, the
contact is opened.
CLS
18.2 List of Parameters
Summary of Contents for UTAdvanced UP55A
Page 3: ......
Page 21: ...Blank Page ...
Page 37: ...Blank Page ...
Page 47: ...Blank Page ...
Page 125: ...Blank Page ...
Page 147: ...Blank Page ...
Page 155: ...8 8 IM 05P02C41 01EN Intentionally blank 8 1 Setting Control Mode CTLM ...
Page 159: ...8 12 IM 05P02C41 01EN Intentionally blank 8 1 Setting Control Mode CTLM ...
Page 167: ...8 20 IM 05P02C41 01EN Intentionally blank 8 1 Setting Control Mode CTLM ...
Page 175: ...8 28 IM 05P02C41 01EN Intentionally blank 8 1 Setting Control Mode CTLM ...
Page 221: ...Blank Page ...
Page 275: ...Blank Page ...
Page 351: ...Blank Page ...
Page 381: ...Blank Page ...
Page 403: ...Blank Page ...
Page 491: ...Blank Page ...
Page 505: ......
Page 513: ...Blank Page ...
Page 515: ...Blank Page ...