18-23
IM 05P02C41-01EN
Parameters
18
PV Input Setting Menu (Menu: PV) (Continued from previous page)
Parameter
symbol
Name
Display
level
Setting range
Initial
value
SDP
PV input scale
decimal point
position
EASY
0: No decimal place
1: One decimal place
2: Two decimal places
3: Three decimal places
4: Four decimal places
Depends
on the
input type
SH
Maximum
value of PV
input scale
EASY
-19999 to 30000, (SL<SH), | SH - SL | ≤
30000
Depends
on the
input type
SL
Minimum value
of PV input
scale
EASY
Depends
on the
input type
BSL
PV input
burnout action
STD
OFF: Disable
UP: Upscale
DOWN: Downscale
Depends
on the
input type
RJC
PV input
reference
junction
compensation
PRO
OFF: RJC OFF
ON: RJC ON
ON
ERJC
PV input
external RJC
setpoint
PRO
-10.0 to 60.0 (°C)
0.0
A.BS
PV analog
input bias
STD
-100.0 to 100.0% of PV input range span
(EUS)
0.0 % of
PV input
range
span
A.FL
PV analog
input filter
STD
OFF, 1 to 120 s
OFF
A.SR
PV analog
input square
root extraction
PRO
OFF: No square root extraction.
1: Compute the square root. (The slope
equals “1.”)
2: Compute the square root. (The slope
equals “0.”)
OFF
A.LC
PV analog
input low signal
cutoff
PRO
0.0 to 5.0%
1.0%
18.2 List of Parameters
Summary of Contents for UTAdvanced UP55A
Page 3: ......
Page 21: ...Blank Page ...
Page 37: ...Blank Page ...
Page 47: ...Blank Page ...
Page 125: ...Blank Page ...
Page 147: ...Blank Page ...
Page 155: ...8 8 IM 05P02C41 01EN Intentionally blank 8 1 Setting Control Mode CTLM ...
Page 159: ...8 12 IM 05P02C41 01EN Intentionally blank 8 1 Setting Control Mode CTLM ...
Page 167: ...8 20 IM 05P02C41 01EN Intentionally blank 8 1 Setting Control Mode CTLM ...
Page 175: ...8 28 IM 05P02C41 01EN Intentionally blank 8 1 Setting Control Mode CTLM ...
Page 221: ...Blank Page ...
Page 275: ...Blank Page ...
Page 351: ...Blank Page ...
Page 381: ...Blank Page ...
Page 403: ...Blank Page ...
Page 491: ...Blank Page ...
Page 505: ......
Page 513: ...Blank Page ...
Page 515: ...Blank Page ...