6-33
IM 05P02C41-01EN
Monitoring and Control of Regular Operations
6
Manual PID Tuning Procedure
(1) In principle, auto-tuning must be used.
(2) Tune PID parameters in the order of P, I, and D. Adjust a numeric slowly by
observing the result, and keep notes of what the progress is.
(3) Gradually reduce P from a larger value. When the PV value begins to oscillate, stop
tuning and increase the value somewhat.
(4) Also gradually reduce I from a larger value. When the PV value begins to oscillate (with
long period), stop tuning and increase the value somewhat.
(5) Gradually increase D from a smaller value. When the PV value begins to oscillate (with
short period), stop tuning and lower the value slightly.
Reference Values for Manual Tuning of Temperature, Pressure, and Flow Rate
Setting range
(reference)
Initial value for tuning (reference)
Pressure
P
100 to 300%
200%
I
5 to 30 s
15 s
D
OFF
OFF
Flow rate
P
100 to 240%
150%
I
8 to 30 s
20 s
D
OFF
OFF
Temperature
(electric
furnace)
P
1 to 20%
5%
I
180 to 600 s
240 s
D
1/4 to 1/6 of I
60 s
6.3 Adjusting PID Manually
Summary of Contents for UTAdvanced UP55A
Page 3: ......
Page 21: ...Blank Page ...
Page 37: ...Blank Page ...
Page 47: ...Blank Page ...
Page 125: ...Blank Page ...
Page 147: ...Blank Page ...
Page 155: ...8 8 IM 05P02C41 01EN Intentionally blank 8 1 Setting Control Mode CTLM ...
Page 159: ...8 12 IM 05P02C41 01EN Intentionally blank 8 1 Setting Control Mode CTLM ...
Page 167: ...8 20 IM 05P02C41 01EN Intentionally blank 8 1 Setting Control Mode CTLM ...
Page 175: ...8 28 IM 05P02C41 01EN Intentionally blank 8 1 Setting Control Mode CTLM ...
Page 221: ...Blank Page ...
Page 275: ...Blank Page ...
Page 351: ...Blank Page ...
Page 381: ...Blank Page ...
Page 403: ...Blank Page ...
Page 491: ...Blank Page ...
Page 505: ......
Page 513: ...Blank Page ...
Page 515: ...Blank Page ...