7-12
IM 05P02C41-01EN
Initial value of eatch control mode
Control mode
Group-1 PYS Goup-2 PYS Group-3 and -4 PYS
Single-loop control
PV
OFF
OFF
Cascade primary-loop control
PV
OFF
OFF
Cascade control
PV
RSP
OFF
Loop control with PV switching
PV
OFF
OFF
Loop control with PV auto-selector
PVIN
OFF
OFF
7.1.5 Setting Ratio bias/filter
Description
Ratio bias computing performs ratio computation and bias addition for remote setpoints.
SP = Remote input x Remote input ratio (RT) + Remote input bias (RBS)
Setting Details
Parameter
symbol
Name
Display
level
Setting range
Menu symbol
RT
Remote input ratio
STD
0.001 to 9.999
SPS
RBS
Remote input bias
STD
100.0 to 100.0% of PV
input range span (EUS)
RFL
Remote input filter
STD
OFF, 1 to 120 s
Note 1: In Cascade control, PV input terminal is for Loop 1 and RSP remote input terminal is for
Loop 2. The LP2 lamp is lit while the Loop-2 parameter is displayed.
7.1 Setting Functions of PV Input, Remote Input, and Auxiliary Analog Input
Summary of Contents for UTAdvanced UP55A
Page 3: ......
Page 21: ...Blank Page ...
Page 37: ...Blank Page ...
Page 47: ...Blank Page ...
Page 125: ...Blank Page ...
Page 147: ...Blank Page ...
Page 155: ...8 8 IM 05P02C41 01EN Intentionally blank 8 1 Setting Control Mode CTLM ...
Page 159: ...8 12 IM 05P02C41 01EN Intentionally blank 8 1 Setting Control Mode CTLM ...
Page 167: ...8 20 IM 05P02C41 01EN Intentionally blank 8 1 Setting Control Mode CTLM ...
Page 175: ...8 28 IM 05P02C41 01EN Intentionally blank 8 1 Setting Control Mode CTLM ...
Page 221: ...Blank Page ...
Page 275: ...Blank Page ...
Page 351: ...Blank Page ...
Page 381: ...Blank Page ...
Page 403: ...Blank Page ...
Page 491: ...Blank Page ...
Page 505: ......
Page 513: ...Blank Page ...
Page 515: ...Blank Page ...