8-47
IM 05P02C41-01EN
Control Functions
Positive Dead Band
0%
Dead
band
(DB)
Dead
band
(DB)
Cooling-side control output (%)
Heating-side control output (%)
0%
50%
Control computation output
100%
100%
Cooling-side
control output
high limit
(OHc)
Heating-side
control output
high limit
(OH)
0%
100%
0%
50%
100%
(OUT)
Negative Dead Band
0%
0%
50%
100%
100%
0%
100%
0%
50%
100%
Dead
band
(DB)
Dead
band
(DB)
Cooling-side control output (%)
Heating-side control output (%)
Control computation output
Cooling-side
control output
high limit
(OHc)
Heating-side
control output
high limit
(OH)
(OUT)
CAUTION
• Set the ratio of the heating-side proportional band (P) to the cooling-side
proportional band (Pc) to within 1 to 5.
• Setting the heating-side or cooling-side integral time (I or Ic) to “OFF” results in
the integral time of both sides being set to “OFF.”
8
8.2 Setting Control Type (CNT)
Summary of Contents for UTAdvanced UP55A
Page 3: ......
Page 21: ...Blank Page ...
Page 37: ...Blank Page ...
Page 47: ...Blank Page ...
Page 125: ...Blank Page ...
Page 147: ...Blank Page ...
Page 155: ...8 8 IM 05P02C41 01EN Intentionally blank 8 1 Setting Control Mode CTLM ...
Page 159: ...8 12 IM 05P02C41 01EN Intentionally blank 8 1 Setting Control Mode CTLM ...
Page 167: ...8 20 IM 05P02C41 01EN Intentionally blank 8 1 Setting Control Mode CTLM ...
Page 175: ...8 28 IM 05P02C41 01EN Intentionally blank 8 1 Setting Control Mode CTLM ...
Page 221: ...Blank Page ...
Page 275: ...Blank Page ...
Page 351: ...Blank Page ...
Page 381: ...Blank Page ...
Page 403: ...Blank Page ...
Page 491: ...Blank Page ...
Page 505: ......
Page 513: ...Blank Page ...
Page 515: ...Blank Page ...