10-24
IM 05P02C41-01EN
10.14 Changing Current Output Range
Description
The analog output type can be selected from among 4 to 20, 0 to 20, 20 to 4, or 20 to 0
mA.
Setting Details
Parameter
symbol
Name
Display
level
Setting range
Menu symbol
OU.A
OUT current output
range
STD
4-20: 4 to 20 mA,
0-20: 0 to 20 mA,
20-4: 20 to 4 mA,
20-0: 20 to 0 mA
OUT
OU2.A
OUT2 current output
range
STD
RET.A
RET current output
range
STD
Parameters and Corresponding Terminals
OU.A
OUT terminal
OU2.A
OUT2 terminal
RET.A
RET terminal