7-15
IM 05P02C41-01EN
Input (PV
, Remote, and
Auxiliary
Analog) Functions
7.4 Using Larger, Smaller, Average, or Difference
of Two to Four Inputs as PV
Description
Loop control with PV auto-selector function automatically selects or calculates the larger,
smaller, average, or difference of multiple (two to four) inputs and uses the result as PV.
The larger, smaller, and average are automatically computed based on the specified
number of inputs.
For the input difference, the difference between input 1 and input 2 is computed.
Input 1: PV terminal input
Input 2: RSP terminal input
Input 3: AIN2 auxiliary analog input
Input 4: AIN4 auxiliary analog input
► Function block diagram for Loop control with PV auto-selector; 8.1.5 Loop Control with PV Auto-
selector, Heating/cooling Loop Control with PV Auto-selector, and Position Proportional Loop
Control with PV Auto-selector
Setting Details
Parameter
symbol
Name
Display
level
Setting range
Menu symbol
PV.AS
Input computation
selection
STD
0: Max. value
1: Min. value
2: Ave. value
3: Input 1 - Input 2
4: Input 2 - Input 1
MPV
PV.NU
Number of inputs
STD
2: Use Input 1 and Input 2
3: Use Input 1, Input 2, and
Input 3
4: Use 4 inputs
7
Summary of Contents for UTAdvanced UP55A
Page 3: ......
Page 21: ...Blank Page ...
Page 37: ...Blank Page ...
Page 47: ...Blank Page ...
Page 125: ...Blank Page ...
Page 147: ...Blank Page ...
Page 155: ...8 8 IM 05P02C41 01EN Intentionally blank 8 1 Setting Control Mode CTLM ...
Page 159: ...8 12 IM 05P02C41 01EN Intentionally blank 8 1 Setting Control Mode CTLM ...
Page 167: ...8 20 IM 05P02C41 01EN Intentionally blank 8 1 Setting Control Mode CTLM ...
Page 175: ...8 28 IM 05P02C41 01EN Intentionally blank 8 1 Setting Control Mode CTLM ...
Page 221: ...Blank Page ...
Page 275: ...Blank Page ...
Page 351: ...Blank Page ...
Page 381: ...Blank Page ...
Page 403: ...Blank Page ...
Page 491: ...Blank Page ...
Page 505: ......
Page 513: ...Blank Page ...
Page 515: ...Blank Page ...