8-72
IM 05P02C41-01EN
8.13 Setting Controller Action at Power ON (Restart Mode)
Description
For details, see Chapter 15, “Power Failure Recovery Processing.”
Setting Details
Parameter
symbol
Name
Display
level
Setting range
Menu symbol
R.MD
Restart Mode
STD
CONT: Continue action set before
power failure. (Continue operation
mode.)
MAN: Start from MAN. (Continue
operation mode.)
RESET: Start from AUTO and RESET.
Outputs the preset output value.
Set how the controller should recover
from a power failure of 5 seconds or
more.
SYS
Operation mode: PROG, RESET, LOCAL, REMOTE
The preset output (PO) is output in MAN or RESET mode.