11-8
IM 05P02C41-01EN
Analog Input RSP High limit Alarm and Analog Input RSP Low Limit Alarm
These alarms monitor the input value after the analog input computation process (entrance
to the input ladder calculation) is completed.
Analog input
ON
OFF
ON
Contact type in the figure above: Energized when an event occurs (factory default).
Alarm hysteresis
Alarm hysteresis
OFF
Time
Analog input
RSP high limit
alarm setpoint
Analog input
RSP low limit
alarm setpoint
Analog input
RSP high limit
alarm output
Analog input
RSP low limit
alarm output
Analog Input AIN2 High Limit Alarm and Analog Input AIN2 Low Limit Alarm
These alarms monitor the input value after the analog input computation process (entrance
to the input ladder calculation) is completed.
Aux. analog (AIN2) input
ON
OFF
ON
Contact type in the figure above: Energized when an event occurs (factory default).
Alarm hysteresis
Alarm hysteresis
OFF
Time
Analog input
AIN2 high limit
alarm setpoint
Analog input
AIN2 low limit
alarm setpoint
Analog input
AIN2 high limit
alarm output
Analog input
AIN2 low limit
alarm output
11.1 Setting Alarm Type
Summary of Contents for UTAdvanced UP55A
Page 3: ......
Page 21: ...Blank Page ...
Page 37: ...Blank Page ...
Page 47: ...Blank Page ...
Page 125: ...Blank Page ...
Page 147: ...Blank Page ...
Page 155: ...8 8 IM 05P02C41 01EN Intentionally blank 8 1 Setting Control Mode CTLM ...
Page 159: ...8 12 IM 05P02C41 01EN Intentionally blank 8 1 Setting Control Mode CTLM ...
Page 167: ...8 20 IM 05P02C41 01EN Intentionally blank 8 1 Setting Control Mode CTLM ...
Page 175: ...8 28 IM 05P02C41 01EN Intentionally blank 8 1 Setting Control Mode CTLM ...
Page 221: ...Blank Page ...
Page 275: ...Blank Page ...
Page 351: ...Blank Page ...
Page 381: ...Blank Page ...
Page 403: ...Blank Page ...
Page 491: ...Blank Page ...
Page 505: ......
Page 513: ...Blank Page ...
Page 515: ...Blank Page ...