9-10
IM 05P02C41-01EN
Example of a soak segment for segment No. 3 of the control program pattern
When ramp-prioritized PV start is the selected start condition, the control program pattern
ramp is the start trigger. The control program pattern contains points A1 to E1.
The retransmission program pattern will start at the same time as the control program
pattern does. For example, if A1 is the selected start point for the control program
pattern, A2 will be that for the retransmission program pattern.
D1
E1
E2
D2
B1
C1
C2 B2
TSP
SSP
Segment 1
Segment 2
Segment 3
a
b
c
d
e
A1
A2
Program pattern
for control
Program pattern
for retransmission
Program operation start (PRG)
Time
Setpoint
Program start point is determined by the control PV as follows.
PV at start
Operation-starting point for
control
Operation-starting point for
retransmission
a
A1
A2
b
B1
B2
c
C1
C2
d
D1
D2
e
E1 (SSP)
E2 (SSP)
9.3 Setting the Program Starting Conditions (STC)
Summary of Contents for UTAdvanced UP55A
Page 3: ......
Page 21: ...Blank Page ...
Page 37: ...Blank Page ...
Page 47: ...Blank Page ...
Page 125: ...Blank Page ...
Page 147: ...Blank Page ...
Page 155: ...8 8 IM 05P02C41 01EN Intentionally blank 8 1 Setting Control Mode CTLM ...
Page 159: ...8 12 IM 05P02C41 01EN Intentionally blank 8 1 Setting Control Mode CTLM ...
Page 167: ...8 20 IM 05P02C41 01EN Intentionally blank 8 1 Setting Control Mode CTLM ...
Page 175: ...8 28 IM 05P02C41 01EN Intentionally blank 8 1 Setting Control Mode CTLM ...
Page 221: ...Blank Page ...
Page 275: ...Blank Page ...
Page 351: ...Blank Page ...
Page 381: ...Blank Page ...
Page 403: ...Blank Page ...
Page 491: ...Blank Page ...
Page 505: ......
Page 513: ...Blank Page ...
Page 515: ...Blank Page ...